Lennox Hearth Brentwood SP User Manual

Page 10

Advertising
background image

Facing

1. Combustible material must be installed flush

with the fireplace. It may not project in front

of and on the fireplace (i.e. the steel facade

of the fireplace) (Figure 10).

2. Non-combustible materials such as brick,

stone or ceramic tile may project in front of

and onto the fireplace facing (Figure 11).

Mantel

The mantel must be installed at least 45”

(1143 mm) above the base of the fireplace

(Figure 10).

Figure 10

Figure 11

1/2” Drywall

2” X 3” Min.

Spacer

Spacer

2” X 3” Min.

1/2” Drywall

Mantel

45”

(1143mm)

Min.

Door

Non-Combustible Facing

Figure 9

Insulated Chase Construction

Floor

Ceiling

Wall

• Must have the same firestopping

resistance as adjacent wall.

• Must have the same insulation as

adjacent ceiling.

• Follow local rules regarding framing

construction.

7’

(2.1 m)

Min.

Note: Floor and wall below the attic must be

insulated using the same insulation.

Attic Radiation

Shield

Roof Support

Storm Collar

Flashing

Drywall or Any Rigid

Material

2 x 4

FIREPLACE

1/2” Plywood

6’ 8”

(2 m)

Min.

Firestop

Insulate Joists

Same As Ceiling

Draft Stops

Firestop

CTDT

Termination

Note: Non-

Combustible

Chase

Flashing

Must Be

Used To

Cover

Chase

Opening

Optional

Insulation

In Outside

Walls Of

Chase

Solid

Continuous

Surface

Outside

Base

Insulation

(Thermal Barrier)

8'

Level

8’

(2.4 m)

Level

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

10