Lightolier LOT Series User Manual

Lot series, Va s, Ingle

Advertising
background image

LOT Series

1.5-4.2

K

VA S

INGLE

P

HASE

UPS

Page 1 of 2

Job Information

Type:

Job Name:

Cat. No.:

Notes:

LOT

A

C

Overall Characteristics

Features: 90% throughput

efficiency with 85% emergency

efficiency. Operating

temperature range 32ºF

(0ºC) to 104ºF (40ºC). Fault

current rating of 42 kAIC.

Audible noise less than 50 dB

at 3 ft on “A” weighted scale.

Automatic low battery voltage

disconnect. Double conversion

with no interruption. Solid

state pulse width modulated

inverter. Internal, make before

break maintenance by-pass.

Standard UL 924 compliant,

90 minute battery back up.

UL 924 auxiliary equipment

10 and 20 minute back up

available. Microprocessor

control and diagnostic system.

LED array system status panel.

Fault annunciating audible

alarm. Current limiting start

sequence. Optional output

circuit breakers (OCB) and

circuit breakers with trip alarm

(OCBA). Optional normally

off load (NOL) energizes only

during power outage, normally

off load with time delay (TDT)

also available. Free standing

NEMA 1 enclosure. Lockable

control access panel. Seismic

anchoring compatible.

Application: The solid state

pulse width modulated (PWM)

inverter offers enhanced load

compatibility. It operates

incandescent, magnetic, and

electronic ballast fluorescent,

high power factor compact

fluorescent and high intensity

discharge (HID) luminaries.

Provides conditioned,

uninterruptible power for

other types of critical loads.

Consult factory for non-lighting

load applications.

Input: Input power factor

correcting to 0.99. Frequency

range 60 Hz, ±2.5 Hz. Input

harmonic current distortion

< 5%THD. UL1449, ANSI/IEEE

C62.41 surge suppression.

Output: Sine wave output.

Voltage regulation ±2%.

Frequency regulation is

synchronized to utility and free

running 60 Hz, ±0.5%. Output

voltage distortion maximum

3% THD with linear load. Load

power factor capability 0.7 lead

to 0.7 lag. Overload capability

125% for 10 seconds.

Code Compliance

UL 924 and UL 924 auxiliary

equipment listed.

Warranty

Lightolier will provide parts

and on-site labor for the first

12 months following start-

up of the product, and parts

only for an additional 12

months. If factory start-up is

not executed within 120 days

of shipment, Lightolier will

provide a parts warranty for

12 months from the date of

shipment. Consult factory for

extended warranty and service

option.

B

1.5-3.5 kVA

36"

24"

72"

4.2 kVA

36"

24"

80"

Width (A)

Depth (B)

Height (C)