5.4.

Server Side Map Descriptors

5.4.1. FieldServer

Specific

Map Descriptor Parameters

Column Title

Function

Legal Values

Map_Descriptor_Name

Name of this Map
Descriptor

Up to 32 alphanumeric
characters

Data_Array_Name

Name of Data Array where
data is to be stored in the
FieldServer

One of the Data Array
names from “Data Array”
section above

Data_Array_Offset

Starting location in Data
Array

0 to maximum specified in
“Data Array” section above

Function

Function of Server Map
Descriptor

Server

5.4.2.

Driver Specific Map Descriptor Parameters

Column Title

Function

Legal Values

Node_Name

Name of Node to fetch
data from

One of the node names
specified in “Server Node
Descriptor” above

Data_Type

Data type in PLC

Note 2

Object_ID

Address of the object

0, 1, 2, 3, …

Property

The object property to
read

Present value

Units

The object units

See Error! Reference source
not found.

Data_Array_Low_Scale*

Scaling zero in Data
Array

-32767 to 32767, 0

Data_Array_High_Scale*

Scaling max in Data
Array

-32767 to 32767, 100

Node_Low_Scale*

Scaling zero in
Connected Node

-32767 to 32767, 0

Node_High_Scale*

Scaling max in
Connected Node

-32767 to 32767, 100

Active_Text

2

Specify the Active Text
property of the Object

Any legal BACnet ASCII string

Inactive_Text1

Specify the Inactive Text
property of the Object

Any legal BACnet ASCII string

Relinquish_Default1

Specify the startup
Relinquish_Default
Property value for this

Any legal BACnet ASCII string

Note 2

AI

- ANALOG INPUT

BV

- BINARY_VALUE

AO

- ANALOG_OUTPUT

MI

- MULTI_STATE_INPUT

AV

- ANALOG_VALUE

MO

- MULTI_STATE_OUTPUT

BI

- BINARY_INPUT

MV

- MULTI_STATE_VALUE

BO

- BINARY_OUTPUT

DI

- DIGITAL_INPUT

DO

- DIGITAL_OUTPUT

2

See the BACnet DFS to determine if a particular object supports this property