FS-8704-02_BacnetEthernet.doc Driver Manual

Page 6 of 20


FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com

Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]

4.

Configuring the FieldServer as a BACnet Ethernet Client

For a detailed discussion on FieldServer configuration, please refer to the FieldServer
Configuration Manual. The information that follows describes how to expand upon the factory
defaults provided in the configuration files included with the FieldServer (See “.csv” sample files
provided with the FieldServer).

This section documents and describes the parameters necessary for configuring the FieldServer
to communicate with a BACnet Ethernet Server.

4.1. Data

Arrays

Note that in the tables, * indicates an optional parameter, with the bold legal value being the
default.

Section Title

Data_Arrays

Column Title

Function

Legal Values

Data_Array_Name

Provide name for Data Array

Up to 15 alphanumeric
characters

Data_Array_Format

Provide data format. Each Data Array
can only take on one format.

FLOAT, BIT

Data_Array_Length

Number of Data Objects. Must be
larger than the data storage area
required by the Map Descriptors for
the data being placed in this array.

1-10,000

Example

// Data Arrays

Data_Arrays

Data_Array_Name,

Data_Format,

Data_Array_Length

DA_AI_01,

Float,

200

DA_AO_01,

Float,

200

DA_DI_01,

Bit,

200

DA_DO_01,

Bit,

200

4.2.

Client Side Connection Descriptions

Section Title

Adapter

Column Title

Function

Legal Values

Adapter

Adapter Name

N1, N2

1

Protocol

Specify protocol used

Bacnet_Eth

Poll Delay*

Time between internal polls

0-32000s; 0.500s

1

Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction

manual for details of the ports available on specific hardware.