Installation, Vantage 500 cummins – Lincoln Electric 500 User Manual

Page 15

Advertising
background image

A-7

INSTALLATION

VANTAGE 500 CUMMINS

A-7

2. Take necessary steps to assure load is limited to

the capacity of the VANTAGE 500 CUMMINS by
installing a 50 amp, 240 VAC double pole circuit
breaker. Maximum rated load for each leg of the
240 VAC auxiliary is 50 amps. Loading above the
rated output will reduce output voltage below the
allowable -10% of rated voltage which may damage
appliances or other motor-driven equipment and
may result in overheating of the VANTAGE 500
CUMMINS engine.

3. Install a 50 amp 120/240 VAC plug (NEMA Type

14-50R) to the double-pole circuit breaker using #6
or #4 conductor cable of the desired length. (The 50
amp, 120/240 VAC plug is available in the optional
K802N or K802R plug kits or by itself as T12153-9.)

4. Plug this cable into the 50 Amp 120/240 Volt recep-

tacle on the VANTAGE 500 CUMMINS case front.

Figure A.2 Connection of the VANTAGE 500 CUMMINS to Premises Wiring

240 Volt

60 Hz.

3-Wire

Service

POWER

COMPANY

METER

240 VOLT

120 VOLT

120 VOLT

LOAD

N

NEUTRAL
BUS

GROUND

PREMISES

DISCONNECT AND

SERVICE

OVERCURRENT

PROTECTION

GND

N

NOTE: No. 6 COPPER CONDUCTOR CABLE SEE

NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE

SIZE RECOMMENDATIONS.

240 VOLT

GROUNDED CONDUCTOR

50AMP

240 VOLT

DOUBLE

POLE

CIRCUIT

BREAKER

DOUBLE POLE DOUBLE THROW
SWITCH RATING TO BE THE SAME
AS OR GREATER THAN PREMISES

SERVICE OVERCURRENT

PROTECTION.

50 AMP, 120/240

VOLT PLUG

NEMA TYPE 14-50

50 AMP, 120/240 VOLT

RECEPTACLE