On every Battery, Power or Control Module are two LEDs to help inform the user of the module status.
Refer to the chart below for Power and Battery Modules:

Status LED

(Green)

Fault LED

( Amber)

Module Status

OFF

OFF

Module not inserted into frame.
System is OFF.

OFF

ON

Module is initializing (max 10 seconds*).

FLASHING

OFF

Normal Operation

FLASHING

FLASHING

Module is in start-up qualification mode, or module warning. **

FLASHING

ON

Module failed, is off-line and module control is functioning.

OFF

FLASHING

ON

OFF

ON

ON

ON

FLASHING


Abnormal operation, re-insert module. If this persists, call Liebert Global
Services at

1-800- 543-2378.

* If this persists for more than 10 seconds, check to verify the lever is in the down position or the module is faulty.
** If both Green and Amber LEDs are flashing for more than 30 seconds, then re-insert module.