Module led indication – Liebert Nfinity 208 V / 240 V 60Hz User Manual
Page 35
33
On every Battery, Power or Control Module are two LEDs to help inform the user of the module status.
Refer to the chart below for Power and Battery Modules:
Status LED
(Green)
Fault LED
( Amber)
Module Status
OFF
OFF
Module not inserted into frame.
System is OFF.
OFF
ON
Module is initializing (max 10 seconds*).
FLASHING
OFF
Normal Operation
FLASHING
FLASHING
Module is in start-up qualification mode, or module warning. **
FLASHING
ON
Module failed, is off-line and module control is functioning.
OFF
FLASHING
ON
OFF
ON
ON
ON
FLASHING
Abnormal operation, re-insert module. If this persists, call Liebert Global
Services at
1-800- 543-2378.
* If this persists for more than 10 seconds, check to verify the lever is in the down position or the module is faulty.
** If both Green and Amber LEDs are flashing for more than 30 seconds, then re-insert module.
Module LED Indication