Occasionally a control, battery or power module
will need to be removed or replaced. Follow the
instructions below when such an event occurs.
To order additional modules, contact your
Liebert representative or call 1-800-LIEBERT.

Removing Modules

1. Remove bezel cover of appropriate module.

When replacing a Power or Battery Module,
verify the faulty module by confirming the
amber LED is lit.


2. If removing a Control or Power Module with

no redundant modules, switch UPS to
manual bypass.


3. Pull out and lift the lever if replacing a

Control or Power Module, then turn fastener
counter-clockwise until it is loosened.


4. Start to pull out module. About 2/3 out it will

stop. Slide module away from the center of
the UPS. Continue to pull until module is
removed. (Seen at right)
Caution: Battery Modules are heavy (66
lbs, 30 kg). Make sure to use two people
when removing a Battery Module.

5. Dispose of module in an environmentally

responsible way that complies with local
codes / regulations or return to Liebert for
proper disposal.


Note: Battery Modules may contain shipping
screws. These screws may be removed and
discarded.