External Battery Cabinets

WARNING: Remove UPS battery fuses and open the Battery
Cabinet circuit breaker before removing the battery cable
connectors cover plate. These connectors contain lethal
voltages when the circuit to the battery is complete.

Standard External Battery Cabinets

Matching stand-alone cabinet(s) can be provided with
additional string(s) of low-maintenance batteries for additional
back-up time in conjunction with the UPS internal battery. Each
cabinet includes a fuse and a circuit breaker disconnect. The
UPS-to-battery cabinet wiring allows for cabinet location directly
adjacent to the UPS module. See Figures below and on the
following page. See Battery Time Curves in Appendix.

Battery

CB (35A)

External

Connectors

Battery

Fuse (30A)

Rear View

Top View

VBD061

3.5-6 kVA

Battery

Fuse

(30A)

Battery

CB (30A)

External

Connectors

Rear
View

VBS061 / VBS062

3.5-6 kVA

Battery

CB (70A)

External

Connectors

Battery

Fuse (70A)

VBD121

8 - 12 kVA

Rear View

Top View

Battery

CB (30A)

Battery

Fuse

(30A)

External

Connectors

Rear View

Top View

VBS122

8-12 kVA

VBD 181

15-18 kVA

Battery

CB (100A)

Access

Plate for

Power

Cable

Entry

Rear View

Top View

(Cover Removed)

Battery
Fuse (100A)

Power Terminal
Block Wire
Range:
(4) #14 - #4 per
Connection

Two Ground
Lugs Wire
Range:
(1) #14 - #1/0
Each

Battery
CB (100A)