Routine Maintenance

The Liebert UPStation S™ UPS should operate for years with minimum maintenance. Keep UPS clean and cool to
enhance system reliability. Occasionally vacuum dust from around ventilation grilles and wipe UPS with a dry cloth. Do
not use liquid or aerosol cleaning fluids.
Periodically check UPS operation by switching off utility power and observing the On Battery message. Do this with only
non-critical loads connected to the unit.

Liebert UPStation S™ Specifications

SYSTEM
Safety Agencies

CSA 22.2, UL 1778 listed

Audible Noise

55 dBA at one meter

Transient/ Surge Protection

Per IEEE 587/ANSI C62.41 Class A&B

Efficiency

Minimum 87% at full load

PHYSICAL CHARACHTERISTICS (See Site Planing Data for dimensions and weight)
Operating Environment

0 degrees C to 40 degrees C

Relative Humidity

0 to 95% relative humidity (non-condensing)

Altitude

5000 feet without derating

AC INPUT
Voltage Range

176 to 264 VAC

Voltage Configuration and Connection

Single phase, 3-wire plus ground (L1-L2-N-G)
Single phase, 2-wire plus ground (L1-N-G)
Three phase, 4-wire plus ground (L1-L2-L3-N-G) (8-18 kVA only)
Three phase, 3-wire plus ground (L1-L2-L3-G) (8-18 kVA only)

Frequency Range

45 Hz to 65 Hz

Current THD

5% THD maximum at full load

Power Factor

.98 typical

AC OUTPUT
Voltage Regulation

Typically less than +/- 2%

Voltage Distortion

Max. 3% THD for linear loads, max. 5% THD for full non-linear
loads

Transient Response

Less than +/- 5% for 100% step load; recovery to within 1% in 50
ms.

Frequency

50 Hz or 60 Hz

Frequency Slew Rate

1 Hz/sec (user-selectable 0.3 to 3 Hz/sec

Frequency Sync Rate

+/- 1 Hz (user selectable +/- 0.1 Hz to 5 Hz

Load Crest Factor

3:1

Overload

125% for 10 minutes, 150% 10 seconds

BATTERY
Type

Sealed, low maintenance, lead acid

Recharge Rate

10 times discharge duration to 95%

Battery Runtime

Minimum 10 minutes at full load

Battery Voltage

Nominal: 192 VDC Float: 220 to 230 VDC