Specifi cations, Permanent connection, Extinguishing control system – LST BCnet216: 19" User Manual

Page 4

Advertising
background image

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED

BC216E_DBL_LST_EN_0804.PDF • PAGE 4

A

Building Safety. Building Security.

Specifi cations

Ambient temperature

-5°C to +50°C

Approval

FT 14/147/3/99 (Austria)

VdS G201017

Control Panel Rack

Dimensions W × H × D

478 × 355 (8 height units) × 244 (mm)

height incl. cable channel: approx. 400 (mm)

Part No.

214230

Order name

Control Panel Rack/8HU RACK216-1E

Display And Operating Front Panel

Current consumption at 24V

typ. 35mA

Connection cable

1.5m

Dimensions W × H × D

478 × 266 (6 height units) × 40 (mm)

Order name

Display And Operating Front Panel ABP216-1E

Fire detection control panel module with power unit

Mains voltage

230VAC +10/-15%, 50Hz

Connection power

300VA

Output voltage

typ. 27.6VDC

Output peak current

typ. 8.4A

Connection of external devices

typ. 6A, site-specifi c

Own current consumption at 24V

typ. 90mA (without optional componentries)

Dimensions W × H × D

233 Ч 355 Ч 104 (mm)

Part No.

214204

Order name

Fire Detection Control Panel Module BCM216-3EPS

Permanent Connection

A variety of peripheral devices can be connected to the

fi re detection control panel BCnet216:

• Fire brigade key safe

• Fire brigade control unit

• Acoustic and optical signaling devices

• External protocol printer

• Remote display and operating panels

• Remote indication unit

• Actuations

• Electronic monitoring system

• Transmitting device for the actuation of pagers via

ESPA protocol

• Modules for remote parameterisation and remote

maintenance via computer newtork, modem or GSM

connection

• Transmitter module for the transmission of messages

via SMS or e-mail

– and much more.

If required, the BCnet216 can be easily expanded to

an extinguishing control panel LCnet216 according to

EN 12094-1. The panel can control up to 127 fl ooding

zones in a maximum of 127 extinguishing systems.

The function of the extinguishing control panel is fully in-

tegrated into the fi re detection control panel BCnet216,

a combined operation is therefore possible.

The LCnet216 is certifi ed to EN 54-2, EN 54-4,

EN 12094-1 and VdS as a pure extinguishing control

panel and as a combined fi re detection and extinguis-

hing control panel.

Optionally, the LCnet216 can be implemented with full

hardware redundancy.

Extinguishing Control System

Advertising