Environmental Specifications

Operating Temperature

0 to 50˚C without derating. However, operating

at or near 50˚C will adversely affect battery life

(refer to your battery specifications for more

information). The recommended operating

temperature is 25˚C.

Operating Altitude

Maximum 1500m (5000 ft) at 50_C without

derating

Storage Temperature

---20 to +70˚C (prolonged storage above 40˚C

will cause rapid battery self-discharge)

Relative Humidity (operating and

storage)

95% maximum noncondensing

Acoustical Noise

75 dBA at a 1m distance

EMI Supression

Meets FCC Part 15 for class A devices

Electrostatic Discharge (ESD)

Immunity

Meets IEC 801---2 specifications. Withstands up

to 25 kV without damage and with no

disturbance or adverse effect to the critical load.

Battery Specifications

These specifications are for batteries supplied by the customer. Refer to Battery

Data section for more information.

Nominal Battery String

Voltage

120 VDC (60 cells)

Float Charging

2.25 VDC per cell

(135 VDC based on 60 cells)

Initialize Charge

150 VDC, when inverter DC link set to 572 VAC

Battery Charge Current

Limit

Limited to 35% of full plus 6 Kw, regardless of actual load

on inverter