Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation

164291261 Rev. F 111503

(ON COMMUNICATIONS

PANEL OF THE UPS)

DB---9 CONNECTOR

TB1 TB2

Figure 9. Wiring an RMP to the UPS

4.

Connect RMP wiring to the terminal block using terminations shown in Table D.

Table D. RMP Wire Terminations

From RMP A

To UPS

Remarks

TB1---4

TB3---1

TWISTED WIRES (4)

TB1---5

TB3---2

TWISTED WIRES (4)

1---2 TURNS PER

TB1---6

TB3---3

1 2 TURNS PER

3 INCHES

TB1---7

TB3---4

From RMP B (if used)

To UPS

Remarks

TB1---4

TB3---5

TWISTED WIRES (4)

TB1---5

TB3---6

TWISTED WIRES (4)

1---2 TURNS PER

TB1---6

TB3---7

1 2 TURNS PER

3 INCHES

TB1---7

TB3---8