Connection with the alarm sensors, Connection with the alarm output – Panasonic WJ-FS309 User Manual

Page 28

Advertising
background image

28

Example:

N.O. specified by ALM INPUT

Notes:

• For detailed pin assignments refer to page 27.
• Leave pin #5 open, or connect it to +5 V when using

Alarm Sensors.

Connection with the Alarm
Output

Pin #9 (open collector) turns to 0 V while the alarm is acti-
vated. This terminal can drive external warning devices
such as a buzzer or lamp of up to 100 mA, 24 V DC. If the
rating exceeds 100 mA, 24 V use a relay as shown in
Example 2.

Example 1:

Direct drive connection

Example 2:

Connection of devices exceeding drive

capacity

Connection with the Alarm
Sensors

Connect alarm sensors to the ALARM/REMOTE connector.
As shown in the tables on page 27, the WJ-FS309/FS409
accepts up to 9 sensors and the WJ-FS316/FS416 up to 16.
The sensors should meet the following specifications:

1. Allowable input voltage:

Non-voltage contact, or 0 V to 5 V DC

2. Input definition:

Specified by ALM INPUT settings, N.O. (Normally
Open/Low active) or N.C. (Normally Closed/High
active)

3. Active duration: Must be longer than 250 ms.

Sensor 8

GND

Alarm
Sensor 1

Alarm
Sensor 16

Buzzer

NO

C

NC

To Buzzer

Relay

+24V

NC: Normally Closed Contact
NO: Normally Open Contact
C: Common