Grounding/Bonding

Install, ground, bond and wire motor according to local
or National Electrical Code requirements.
Permanently ground motor. Use green ground terminal
provided under motor canopy or access plate (See Figure
4); use size and type wire required by code. Connect
motor ground terminal to electrical service ground.
Bond motor to pool structure. Use a solid copper conductor,
size No. 8 AWG (8.4 sq.mm) or larger. Run wire from exter-
nal bonding lug (see Figure 4) to reinforcing rod or mesh.

Connect a No. 8 AWG (8.4 sq.mm) solid copper bonding
wire to the pressure wire connector provided on the
motor housing and to all metal parts of the swimming
pool, spa, or hot tub and to all electrical equipment,
metal piping or conduit within 5 feet (1.5 m) of the inside
walls of swimming pool, spa, or hot tub.

Wiring

NOTICE: 3 phase models require magnetic motor starters
and external overload protection. If in doubt about the
procedure, consult a licensed electrician.
Pump must be permanently connected to circuit. Table I,
Page

8, give correct wire and circuit breaker sizes for the

pump alone. If other lights or appliances are also on the
same circuit, be sure to add their amp loads to pump
amp load before figuring wire and circuit breaker sizes.
(If unsure how to do this or if this is confusing, consult a
licensed electrician.) Use the load circuit breaker as the
master on-off switch.
Install a Ground Fault Circuit Interrupter (GFCI) in circuit;
it will sense a short-circuit to ground and disconnect
power before it becomes dangerous to pool users. For
size of GFCI required and test procedures for GFCI, see
manufacturer’s instruction.
In case of power outage, check GFCI for tripping (which
will prevent normal pump operation). Reset if necessary.
NOTICE: If you do not use conduit when wiring motor,
be sure to seal wire opening on end of motor to prevent
dirt, bugs, etc., from entering.

Risk of dangerous or fatal electrical shock.

Be sure that power to the motor circuit is off before
working on wiring, wiring connections, or motor. Re-in-
stall the motor end cover and all other wiring covers be-
fore turning on the power.

1. Turn off power.
2. Remove the motor end cover.

To Wire a Single Speed, Single Voltage Motor

There are two terminals labeled L1 and L2. Attach the
power leads to these terminals. Either wire may attach to
either terminal.

To Wire a Dual-Voltage Motor

Dual voltage motors have a plug to change from 230 volts
(factory setting) to 115 volts.
1. If you have 230 volts motor supply voltage, confirm

that the plug is set for 230 volts. The arrow on the plug
will point to the 230 volt position. Note that plug only
connects with one prong in this position.

2. If you have 115 volt supply, pull the plug straight up

and place it on the two brass prongs as shown.

NOTE: Arrow is highlighted

for clarity.

To Wire a Two-Speed Motor

Wire the pump as shown in the diagram.

A

A

L2

L2

L1

L1

230V

115V

Bonding
Lug

Green
Ground
Screw

Figure 4 – Typical ground screw and bonding lug
locations.

Figure 5B

-Voltage Change

Plug Set for 115 Volts

Figure 5A -Voltage Change
Plug Set for 230 Volts

Figure 5C: 2-Speed Motor Wiring Diagram

L

2

=

C

O

M

L

1

=

H

I

A

=

L

O

W

A

L2

L1

Power Supply for

Optional Timer.

Low Speed

High Speed

Circuit

Protector

Remote

SPDT

Switch

Ground (Green)

Common

If using timer, Connect
Timer Motor to Low Speed Only

Minimum switch and timer amp rating must equal Branch Fuse
Rating given in "Recommended Fusing and Wiring Data" table.