TABLE I - RECOMMENDED CIRCUIT BREAKER AND WIRING DATA

Serv. to Motor - Dist. in Ft. (M)

Motor

Branch CB

Max Load

Voltage/

0-100'

101-200'

201-300'

HP

Rating Amps

Amps

Hz/Phase

(0-30)

(30-60)

(60-90)

MPRA SERIES – SINGLE SPEED

3/4

20/15

13.4/6.7

115/230/60/1 12/14(3/2) 10/14(5.5/2) 8/14(8.4/2)

1

20/15

15.3/7.6

115/230/60/1

12/14(3/2) 8/14(8.4/2)

6/14(14/2)

1-1/2

25/15

19.2/9.6

115/230/60/1 10/14(5.5/2) 8/14(8.4/2)

6/12(14/3)

2

20

12.0

230/60/1

14(2)

14(2)

12(3)

MPEA SERIES – SINGLE SPEED

3/4

15/15

11.0/5.5

115/230/60/1 14/14(2/2) 10/14(5.5/2) 8/14(8.4/2)

1

20/15

13.8/6.9

115/230/60/1

12/14(3/2) 10/14(5.5/2) 8/14(8.4/2)

1-1/2

25/15

16.0/8.0

115/230/60/1

12/14(3/2) 8/14(8.4/2)

6/14(14/2)

2

15

10.4

230/60/1

14(2)

14(2)

12(3)

2-1/2

15

11.2

230/60/1

14(2)

14(2)

12(3)

MPRA SERIES – TWO SPEED

1-1/2 – 1/4

15

9.2/2.5

230/60/1

14(2)

14(2)

12(3)

MPEA SERIES – TWO SPEED

2 – 1/4

15

10.0/3.0

230/60/1

14(2)

14(2)

12(3)

2-1/2 – 1/2

15

11.3/3.3

230/60/1

14(2)

12(3)

12(3)

MPE SERIES – SINGLE SPEED

1/2

15/15

11.0/5.5

115/230/60/1 14/14(2/2) 10/14(5.5/2) 8/14(8.4/2)

3/4

20/15

13.8/6.9

115/230/60/1

12/14(3/2) 10/14(5.5/2) 8/14(8.4/2)

1

25/15

16.0/8.0

115/230/60/1

12/14(3/2) 8/14(8.4/2)

6/14(14/2)

1-1/2

15

10.4

230/60/1

14(2)

14(2)

12(3)

2

15

11.2

230/60/1

14(2)

14(2)

12(3)

MPE SERIES – TWO SPEED

1-1/2 – 1/4

15

10.0/3.0

230/60/1

14(2)

14(2)

12(3)

2 – 1/3

15

11.3/3.3

230/60/1

14(2)

12(3)

12(3)

AWG

Wire

Size

(mm

2

)

}

AWG

Wire

Size

(mm

2

)

}

AWG

Wire

Size

(mm

2

)

}

AWG

Wire

Size

(mm

2

)

}

AWG

Wire

Size

(mm

2

)

}