PD-3006/12

Power over LAN Solutions

15

Cat. No.: 06-6831-056

Table 3-1: Troubleshooting Steps

Symptom

Corrective Steps

The end device
operates, but
there is no data
link.

1. Verify that the port indicator on the front panel is

continuously lit.

2. If an external power splitter is in use, replace it with a

known-good splitter.

3. Verify that for this link, you are using standard

UTP/FTP Category 5 straight (non-crossover)
cabling, with all four pairs. Check that the link is 100
m or less.

4. Try to re-connect the same end device into a different

port on the same unit or into different unit – if it works,
there is probably a faulty port or RJ-45 connection.

Is it safe to keep
the Midspan
running while a
port indicator is
orange?

This is a safe condition. The orange indication is due to:

1. A device, not compliant to IEEE 802.3af, was detected.
2. Terminals 4/5 and 7/8 are shorted together.
3. Forced external power fed into the port.

During these conditions, port power is disconnected.

Technical Specifications

Physical Specifications

Dimensions

44 x 281 x 248 mm

(h x w x l)

(1.73 x 11.06 x 9.76 inch)

Weight

1.2 kg (3.2 lb)

Environmental Specifications

Temperature

- Operating

0 to 40 °C (32 to 104 °F)

- Storage

-20 to 70 °C (-4 to 158 °F)

Humidity

10 to 90% (non-condensing)

Electrical Specifications

Input Voltage

90 to 264 VAC at 47-63 Hz

Input Current

1.5 A max. at 115 Vac

Total Output Power

92 W max.

Output Power, per Port

15.4 W (not to exceed 92 W total for all ports)

Nominal Output Voltage

44 to 57 VDC