0 operation – Patterson-Kelley MOD-04 User Manual

Page 25

Advertising
background image

Modu-Fire

®

Gas-Fired Boiler

Operation

22

4.0 OPERATION


4.1

G

ENERAL


4.1.1 Control Panel Front







The front of the control panel shows Operating In-
structions and a series of illuminated indicator lights
which show the condition of the boiler.



4.2

L

IGHTING AND

S

HUT

-D

OWN

P

ROCEDURES

Do not use this boiler if any part has been under wa-
ter. Immediately call factory-trained personnel to
inspect the boiler and to replace any part of the con-
trol system and any gas control which has been un-
der water.





4.2.1 Lighting Procedures

1. Utilities: Turn on electric supply to boiler.

Open gas supply valves. Make sure system is
filled with water and turn on circulation pump.

2. Reset Switches: Press reset button on gas pres-

sure switches (attached to main gas valve at
back of boiler) if gas supply was turned off.
Press control reset button after safety lockout.

3. Set desired limit and operating temperature (in-

side control panel).

Main Gas
Cock

Low Gas
Pressure
Switch

Pilot Gas
Cock

Operating
Instructions

Temperature
Control

Indicator Lights

On-Off Switch

Reset Switch

On-Off Switch

High Gas
Pressure
Switch

Cabinet Air
Pressure
Test

Main Gas
Pressure
Test

Pilot Gas
Pressure
Test

Advertising