3.0 Operating the Boiler

8

3.9

Central Heating System Pressure

1. The water pressure in the central heating

system is indicated by the pressure gauge.

2. With the system cold and the boiler not

operating the pressure should be between 0.5

and 1.0 bar. During operation the pressure

should not exceed 2.5 bar, and will normally be

between 1.0 and 2.0 (Figs. 18 & 19).

3. A pressure of 3 or greater indicates a fault.

The safety pressure relief valve will operate, at a

pressure of 3 (Fig. 20). It is important that your

Service Engineer is contacted as soon as

possible.

4. The MINIMUM pressure for correct operation

is 0.5. If the pressure falls below 0.5, this may

indicate a leak on the central heating system

(Fig. 21).

5. The system must be re-pressurised by your

Service Engineer.

3.10

To Shut Off the Boiler

1. For short periods: Turn the selector switch to

the OFF position (Fig. 22).

2. For long periods: Turn off the selector switch

(Fig. 22), electricity and gas supplies.

If your home is to be left unoccupied for long

periods during cold weather the boiler and

whole system should be drained unless there

is additional frost protection.

3. Your installer will advise you about frost

protection and draining the system.

IMPORTANT: When the selector switch is in
the ‘0’ (Off) position the electrical supply to the
boiler is isolated. The boiler will not operate
and the integral timer (if fitted) will require
resetting once the selector switch is set to
either Position (i) or Position (ii).

3.11

Frost Protection Mode

1. The frost protection feature will operate when

the selector switch is in the central heating and

domestic hot water mode.

The gas and electrical supplies to the boiler must

be on and the system pressure must be within

the range described in Section 3.9.

2. If the system temperature falls below 5°C, then

the boiler will fire until the water temperature has

been raised.

3. Further frost protection can be incorporated by

using a frost thermostat to protect the whole

system.

2

1

0

4

3

bar

2

1

0

4

3

bar

2

1

0

4

3

bar

2

1

0

4

3

bar

ON/OFF

Selector Switch

OFF Position

Fig. 22

Normal Pressure (when cold)

Normal Pressure (operating)

Fig. 18

Fault

Fig. 19

Below Minimum

Fig. 20

Fig. 21

Pressure Gauge