4 system event messages – Powerware 9330 User Manual

Page 130

Advertising
background image

11--2

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

11.4

System Event Messages

When a system event occurs, a message appears on the LCD screen in the UPS

Status area. This message is also is written to the Active Events log and may be

added to the Events History Log. The messages are divided into four categories:

Alarms, Notices, Status, and Commands. The following tables contain the events

displayed on the LCD System Events screen of the Control panel.

ALARMS

Message

Horn Phone Relay Log

Indication

Battery Over Voltage

1

No

1

HA Service Required

Battery Over Voltage OK

Off

No

1

HA Condition Cleared

Battery Time is Low

1

No

1

HA User Action Required

Battery Time is Low OK

Off

No

1

HA Condition Cleared

Battery Under Voltage

1

No

1

HA Shutdown Imminent

Battery Under Voltage OK

Off

No

1

HA Condition Cleared

Bypass Calibration Required

1

No

1

HA Service Required

Bypass Calibration Required OK

Off

No

1

HA Condition Cleared

Bypass Control Failure

1

4

1

A

Service Required

Bypass Overheating Shutdown

1

No

1

HA User Action Required

Bypass Overheating Shutdown OK

Off

No

1

HA Condition Cleared

Bypass Overheating Warning

1

No

1

HA Shutdown Imminent

Bypass Overheating Warning OK

Off

No

1

HA Condition Cleared

Bypass Phase Rotation

1

No

1

HA User Action Required

Bypass Phase Rotation OK

Off

No

1

HA Condition Cleared

Bypass Setup Required

1

No

1

HA Service Required

Bypass Setup Required OK

Off

No

1

HA Condition Cleared

Calibrate DC AutoBalance

1

4

1

HA Service Required

Calibrate DC AutoBalance OK

Off

No

1

HA Condition Cleared

Charger Failure

1

4

1

HA Service Required

Charger Failure OK

Off

No

1

HA Condition Cleared

Check Battery

1

No

1

HA User Action Required

Check Battery OK

Off

No

1

HA Condition Cleared

Check Boost

1

4

1

HA Service Required

Check Boost OK

Off

No

1

HA Condition Cleared

Check CSB Setup

1

No

1

HA Service Required

Check CSB Setup OK

Off

No

1

HA Condition Cleared

Check Inverter

1

No

1

HA Service Required

Check Inverter OK

Off

No

1

HA Condition Cleared