NOTE: Customer ground, size 1/0, can be

run in any conduit listed in Table R.

POWER WIRING INSTALLATION NOTES

164201300---1

A---12

Powerware 9330 (10 kVA--40 kVA) Installation and Operation

164201300 REV. G 061502

Table P. Options Cabinet Power Cable Terminations Powerware 9330 (10 kVA---20 kVA)

Terminal Function

Terminal

Function

Size of Pressure

Termination

Vendor

Tightening Torque

N-M (lb-in.)

Type

Screw

AC Input to UPS

L1

Phase A 1 --- #14---#0

Entrelec

2.5-2.9(22-26)

Slotted

p

Rectifier Transformer
(TB1)

L2

Phase B 1 --- #14---#0

Entrelec

2.5-2.9(22-26)

Slotted

(TB1)

L3

Phase C 1 --- #14---#0

Entrelec

2.5-2.9(22-26)

Slotted

AC Input To UPS

Bypass Transformer

L1

Phase A 1 --- #14---#0

Entrelec

2.5-2.9(22-26)

Slotted

Bypass Transformer
(TB1)

L2

Phase B 1 --- #14---#0

Entrelec

2.5-2.9(22-26)

Slotted

(

)

Ll3

Phase C 1 --- #14---#0

Entrelec

2.5-2.9(22-26)

Slotted

N

Neutral

1 --- #14---#0

Entrelec

2.5-2.9(22-26)

Slotted

AC Output from

Output Transformer

X1

Phase A 1 --- #14---#0

Entrelec

2.5-2.9(22-26)

Slotted

Output Transformer

to Critical Load

(TB1)

X2

Phase B 1 --- #14---#0

Entrelec

2.5-2.9(22-26)

Slotted

(TB1)

X3

Phase C 1 --- #14---#0

Entrelec

2.5-2.9(22-26)

Slotted

N

Neutral

1 --- #14---#0

Entrelec

2.5-2.9(22-26)

Slotted

Customer Ground

Ground

Ground

2 --- #14---#1/0

N/A

5.6 (50)

Slotted

Table Q. Options Cabinet Power Cable Terminations Powerware 9330 (25 kVA---40 kVA)

Terminal Function

Terminal

Function

Size of Pressure

Termination

Vendor

Tightening Torque

N-M (lb-in.)

Type

Screw

AC Input to UPS

L1

Phase A 1 --- #14---#0

Entrelec

2.5-2.9(22-26)

Slotted

p

Rectifier Transformer
(TB1)

L2

Phase B 1 --- #14---#0

Entrelec

2.5-2.9(22-26)

Slotted

(TB1)

L3

Phase C 1 --- #14---#0

Entrelec

2.5-2.9(22-26)

Slotted

AC Input To UPS

Bypass Transformer

L1

Phase A 1 --- #14---#0

Entrelec

2.5-2.9(22-26)

Slotted

Bypass Transformer
(TB1)

L2

Phase B 1 --- #14---#0

Entrelec

2.5-2.9(22-26)

Slotted

(TB1)

Ll3

Phase C 1 --- #14---#0

Entrelec

2.5-2.9(22-26)

Slotted

N

Neutral

1 --- #4---#4/0

Entrelec

3.2-3.7(28-33)

6 mm

Allen

AC Output from

Output Transformer

X1

Phase A 1 --- #14---#0

Entrelec

2.5-2.9(22-26)

Slotted

Output Transformer

to Critical Load

X2

Phase B 1 --- #14---#0

Entrelec

2.5-2.9(22-26)

Slotted

to Critical Load

(TB1)

X3

Phase C 1 --- #14---#0

Entrelec

2.5-2.9(22-26)

Slotted

N

Neutral

1 --- #4---#4/0

Entrelec

4-6(35-52)

6 mm

Allen

Customer Ground

Ground

Ground

2 --- #14---1/0

N/A

5.6 (50)

Slotted