Port-a-cool® unit – Port-A-Cool PAC2K16HPVSFC User Manual

Page 17

Advertising
background image

17

2009 PORT-A-COOL® Unit Electric Models

24

2009 PORT-A-COOL® Unit Electric Models

7) Loosen these bolts just enough to slide the old motor out;

don’t remove the bolts completely. Replace with new motor.

8) Thread terminal end of motor wire through switch box

wire opening and plug five-pin connector into switch connec-
tor. IMpORTAnT: Ensure that rubber grommet seal on harness
is properly seated to keep water out of control box.

9) Replace switch box cover.
10) Secure motor wire to fan bracket assembly using new

wire ties.

11) Replace pads by installing from outside toward center

replacing center pad last.

12) Replace blade and screen to front of unit.

puMp REpLACEMEnT

MODELS PAC2K482S, PAC2K361S, PAC2K363S, PAC2K36HPVS, PAC2K24HPVS

1) DISCONNECT POWER and remove pads as shown on page 15.
2) Pump is in lower right of unit. Control box is in upper left. Locate pump wire (å) secured to fan bracket

assembly using plastic wire ties. Cut and remove plastic ties. DO NOT CUT ELECTRICAL WIRES. (Figure 1)

3) Remove screws from control box cover. Unplug pump wire connector. Push rubber grommet on pump

wire through control box opening and remove pump harness wire from control box. (Figure 2)

4) Locate pump in lower right corner of the unit. Remove hose from pump by unscrewing hose connection.

Remove two screws holding pump bracket to the unit housing. Remove entire pump assembly from the unit.

(Figure 3)

5) INSTALL NEW PUMP By REVERSING ABOVE PROCEDURES. (1.) Install new pump on pump bracket and

attach bracket to housing. Replace pump hose. (2.) Thread terminal end of pump wire through control switch
box and plug pump terminal into switch.

6) IMPORTANT: Ensure that rubber grommet seal is in properly seated to keep water out of switch box.
7) Replace switch box cover. Secure pump wire to fan bracket assembly using new bundle ties.
8) Replace pads by installing pads from outside toward center

replacing center pad last. Replace pad flap with screws.

Figure 2

Figure 3

Figure 4

å

(Figure 1)

(Figure 2)

(Figure 3)

DRY BULB

Temp. °C

Temp. °F

23.9 75
26.7 80
29.4 85
32.2 90
35.0 95

37.8 100

TEMP. °F

Difference

Drop

15 10.8
15 10.8
15 10.8
15 10.8
17 12.2
16 11.5

OUTPUT TEMP.

°C °F

17.8 64
20.6 69
23.3 74
26.1 79
28.3 83
31.1 88

60% RH

APPENDIX A

Port-A-Cool® unit

TEMPERATURE OUTPUT CHARACTERISTICS

50% TO 65% RELATIVE HUMIDITY

WET BULB TEMPERATURE

DRY BULB TEMPERATURE

TEMPERATURE DIFFERENCE

TEMPERATURE DROP

OUTPUT TEMPERATURE

Wet Bulb Temperature @ Current Humidity Level
Current Ambient Air Temperature
Dry Bulb Temp Minus Wet Bulb Temp
Temperature Difference Multiplied by 72%
Dry Bulb Temperature Minus Temperature Drop

DRY BULB

Temp. °C

Temp. °F

23.9 75
26.7 80
29.4 85
32.2 90
35.0 95

37.8 100

TEMP. °F

Difference

Drop

22 15.8
20 14.4
22 15.8
21 15.1
22 15.8
22 15.8

OUTPUT TEMP.

°C °F

15.0 59
18.9 66
20.6 69
23.9 75
26.1 79
28.9 84

50% RH

DRY BULB

Temp. °C

Temp. °F

23.9 75
26.7 80
29.4 85
32.2 90
35.0 95

37.8 100

TEMP. °F

Difference

Drop

17 12.2
19 13.7
18 13.0
19 13.7
19 13.7
19 13.7

OUTPUT TEMP.

°C °F

17.2 63
18.9 66
22.2 72
24.4 76
27.2 81
30.0 86

55% RH

A-3

DRY BULB

Temp. °C

Temp. °F

23.9 75
26.7 80
29.4 85
32.2 90
35.0 95

37.8 100

TEMP. °F

Difference

Drop

13 9.4
13 9.4
13 9.4
13 9.4

14 10.1

13 9.4

OUTPUT TEMP.

°C °F

18.9 66
21.7 71
24.4 76
27.2 81
29.4 85
32.8 91

65% RH