2009 PORT-A-COOL® Unit Electric Models

18

puMp REpLACEMEnT

MODELS PAC2K163S, PAC2K163SHD, PAC2K16HPVS

1) DISCONNECT POWER and remove pads as shown on page 15.
2) Remove output tubing from insert fitting on base of pump.

(Figure 1-A)

3) Remove the switch box wiring cover and disconnect the 4-pin

quick release connector from the pump switch assembly.

(Figure 1-B)

4) Remove the pump from the sump tank by removing two screws

that hold the pump cover and pump in place.

(Figure 1-C)
5) Remove the pump cover from old pump install onto the new

pump.

6) Reverse the above procedures to install the new pump.
7) Replace the cooling pads, positioning as shown on the air flow label.
8) Reconnect the unit power and test pump.

puMp REpLACEMEnT

MODEL PAC2K163SFC, PAC2K16HPVSFC

1) Disconnect electrical power to unit and remove pads per page 15.
2) Remove the cover plate on the electrical box to disconnect the

motor quick connect and the zip ties holding it together.

(Figure 1)

3) Remove two screws that hold the strain relief bracket in order to take

the pump cord out of the unit.

(Figure 2)

4) Unscrew the 6” drain pipe located under the fan housing. Slide the

tank outside the caddy base to access the pump bracket.

7) Remove the two screws that hold the bracket to the tank. Remove the

bracket and hose from the pump by loosening the fastening screws

and hose clamp.

8) Install new pump by reversing above steps.

2009 PORT-A-COOL® Unit Electric Models

(Figure 1)

(Figure 1)

(Figure 2)

1-A

1-B

1-C

A-2

APPENDIX A

Port-A-Cool® unit

TEMPERATURE OUTPUT CHARACTERISTICS

30% TO 45% RELATIVE HUMIDITY

DRY BULB

Temp. °C

Temp. °F

26.7 80
29.4 85
32.2 90
35.0 95

37.8 100

40.6 105

TEMP. °F

Difference

Drop

34 24.5
35 25.2
35 25.2
36 25.9
37 26.6
38 27.4

OUTPUT TEMP.

°C °F

13.3 56
15.6 60
18.3 65
20.6 69
22.8 73
25.6 78

DRY BULB

Temp. °C

Temp. °F

23.9 75
26.7 80
29.4 85
32.2 90
35.0 95

37.8 100

TEMP. °F

Difference

Drop

30 21.6
31 22.3
30 21.6
32 23.0
32 23.0
33 23.8

OUTPUT TEMP.

°C °F

11.7 53
14.4 58
17.2 63
19.4 67
22.2 72
24.4 76

WET BULB TEMPERATURE

DRY BULB TEMPERATURE

TEMPERATURE DIFFERENCE

TEMPERATURE DROP

OUTPUT TEMPERATURE

Wet Bulb Temperature @ Current Humidity Level
Current Ambient Air Temperature
Dry Bulb Temp Minus Wet Bulb Temp
Temperature Difference Multiplied by 72%
Dry Bulb Temperature Minus Temperature Drop

30% RH

35% RH

DRY BULB

Temp. °C

Temp. °F

29.4 85
32.2 90
35.0 95

37.8 100
40.6 105
43.3 110

TEMP. °F

Difference

Drop

27 19.4
28 20.2
29 20.9
27 19.4
29 20.9
28 20.2

OUTPUT TEMP.

°C °F

18.9 66
21.1 70
23.3 74
27.2 81
28.9 84
32.2 90

40% RH

DRY BULB

Temp. °C

Temp. °F

29.4 85
32.2 90
35.0 95

37.8 100
40.6 105
43.3 110

TEMP. °F

Difference

Drop

24 17.3
25 18.0
25 18.0
25 18.0
25 18.0
25 18.0

OUTPUT TEMP.

°C °F

20.0 68
22.2 72
25.0 77
27.8 82
30.6 87
33.3 92

45% RH