IMPORTANT: Make sure the electrical
characteristics are the same on the motor
nameplate and the power source, and make
sure the circuit on which the jointer will be used
is properly fused and that the wire size is
correct.

Converting from 230 Volt to 460 Volt

(Three Phase Only)

Consult the wiring diagram inside the starter box
cover. A diagram is also included on pages 37-
38 of this manual. The Jointer must comply with
all local and national codes after being wired.

1. Remove the starter box cover and adjust the

dial on the relay (see Figure 10) as close as
possible to the amperage of the Jointer
motor at 460V, as listed on the motor plate.

2. Move the fuse (Figure 10) from the 230V

slot to the 460V slot.

3. Re-connect the incoming leads to the motor

for 460 volt operation, as shown in the
wiring diagram.

4. If using a plug, install a proper UL/CSA

listed plug suitable for 460 volt operation.

Three-Phase Test Run

On the three-phase unit, after wiring has been
completed, you should check that the incoming
leads have been connected properly:

1. Connect machine to power source and

press the start button (make sure cutterhead
is clear of all obstructions!).

2. The cutterhead should rotate clockwise as

viewed from the front of the machine. If the
cutterhead rotation is incorrect, press the

stop button and disconnect machine from
power.

3. Switch any two of the three leads to the

motor.

Extension Cords

Make sure your extension cord is in good
condition. Always use a cord that is heavy
enough to carry the current your product will
draw; the cord rating must be suitable for the
amperage listed on the machine’s motor plate.
An undersize cord will cause a drop in line
voltage resulting in loss of power and
overheating.

Use the chart in Figure 11 as a general guide in
choosing the correct size cord. If in doubt, use
the next heavier gauge. The smaller the gauge
number, the heavier the cord.






Figure 10

Extension Cord Recommended Gauges (AWG)

Extension Cord Length *

Amps

25

feet

50

feet

75

feet

100

feet

150

feet

200

feet

<

5 16 16 16 14 12 12

5

to

8 16 16 14 12 10 NR

8

to

12 14 14 12 10 NR NR

12

to

15 12 12 10 10 NR NR

15

to

20 10 10 10 NR NR NR

21

to

30 10 NR NR NR NR NR

*based on limiting the line voltage drop to 5V at 150% of the
rated amperes.
NR: Not Recommended.

Figure 11