Msrd 2.5 switching unit – Panasonic PWW 4000 User Manual

Page 12

Advertising
background image

12

MSRD 2.5 switching unit


Rotary current 400 volt, fan 2-speed
maximum electrical capacity 2.5 kW

Wall-mounted, motor protected by integrated thermal con-
tacts in the fan motor.

Design

Plastic housing, protection type IP 41.
Protective insulation in accordance with VDE, plate with
symbols for switching positions, incoming power and
protective conductor terminals, main contactor, control
switch with the functions “Off/Speed 1/Speed 2”, control
fuse, operating light (goes out when there is a fan mal-
function and/or power interruption to the switching unit),
motor output terminals, connection terminals for thermal
contacts and room thermostat.

Switching on again after a problem

Each time the power supply is interrupted or the fan
malfunctions, the fan reset button has to be pressed
once.

Switching and wiring diagram

1 3 5 7 9 11 13 15 17
2 4 6 8 10 12 14 16 18

X X X
X X X X

X X X

X X X

0

D
U

0

D

U

1

2

3

4

7

8

9

10

11

12

13

14

15

16

17

18

5

6

S1

R1

K1

13

14

K1

1 3 5

2 4 6

F1

6,3A

H1

X1

X2

K1

A1

A2

2 3 4

PE L1 L2 L3 N

1 5

7 8 9

6 10

11

12

13

PE U1 V1 W1 U2 V2 W2

TK TK

14

15

RT RT

16

4

4
4

11

1
3
5

13

2
4
6

14

Room thermostat

Thermal

contacts in the

motor

Incoming power

400V/3/N/PE 50HZ

Grounding in accordance with local

requirements

Motor 3~

Thermal protections

for 2 units

Thermal protection

for 3 units

Thermal protection

for 4 units

Connect other thermal

contacts in a row

S1 Control

switch

K1 Switch

contactor

R1 PTC

element

F1 Control

fuse

H1 Operating

light

Group switching

The switching unit is suitable for group switching. Sev-
eral motors wired the same way can be connected to
one switching unit.
The total capacity of the connected motors may not ex-
ceed the permissible switch capacity of the switching
unit. The thermal contacts of all motors are to be con-
nected in a row.

Important information about safe operation

Grounding and earthing or protective wiring and fuse
protection must be done

by the customer in accordance

with the requirements of the VDE as well as the respon-
sible EVU.
The electrical unit connections must be performed by
authorised personnel in the line with the valid require-
ments in compliance with local laws and in accordance
with the wiring diagrams.

Advertising