Technical data – Panasonic PWW 4000 User Manual

Page 9

Advertising
background image

9

Technical Data

PWW 4000 series
Type

4030 - 3

4030 - 4

4050 - 3

4050 - 4

Electrical connection

V

400 / 3~ N

400 / 3~ N

400 / 3~ N

400 / 3~ N

Frequency

Hz

50

50

50

50

Power consumption

kW

0.13 / 0.10

0.13 / 0.10

0.26 / 0.18

0.26 / 0.18

Rated current

A

0.26 / 0.16

0.26 / 0.16

0.52 / 0.29

0.52 / 0.29

Speed

U/min

1340 / 1040

1340 / 1040

1360 / 1020

1360 / 1020

Air capacity

m³/h

2050 / 1640

1850 / 1500

3400 / 2870

3150 / 2770

Sound pressure level

1)

dB(A)

53 / 48

55 / 49

55 / 51

58 / 54

Heating medium connection

inch

R1"

R1¼"

R1"

R1¼"

Heating medium

Pump warm water or pump hot water up to max. 130 °C

Operating pressure

bar

16

16

16

16

Weight

kg

26

27

34

36

PWW 4000 series
Type

4080 - 3

4080 - 4

4100 - 3

4100 - 4

Electrical connection

V

400 / 3~ N

400 / 3~ N

400 / 3~ N

400 / 3~ N

Frequency

Hz

50

50

50

50

Power consumption

kW

0.42 / 0.28

0.42 / 0.28

0.76 / 0.47

0.76 / 0.47

Rated current

A

0.76 / 0.46

0.76 / 0.46

1.50 / 0.81

1.50 / 0.81

Speed

U/min

880 / 670

880 / 670

870 / 650

870 / 650

Air capacity

m³/h

5400 / 4300

4730 / 4700

8250 / 6620

7670 / 6180

Sound pressure level

1)

dB(A)

55 / 49

55 / 49

58 / 54

59 / 55

Heating medium connection

inch

R1¼"

R1¼"

R1½"

R1½"

Heating medium

Pump warm water or pump hot water up to max. 130 °C

Operating pressure

bar

16

16

16

16

Weight

kg

47

51

60

68

1) Measurement at intervals of 5 m, measuring room volume 800 m³, average reverberation time 1.4 s

1) Measurement at intervals of 5 m, measuring room volume 800 m³, average reverberation time 1.4 s

Advertising