Storage, Specifications – Powercom 625A User Manual

Page 16

Advertising
background image

11. Storage
__________________________________________________________
____

10.1 Storage conditions
Store the UPS covered and upright in a cool , dry location, with its battery fully
charged. Before storing, charger the UPS for at least 4 hours. Remove any
accessories in the accessory slot and disconnect any cables connected to the
computer interface port to avoid unnecessary draining the battery.

10.2 Extended storage
During extended storage in environments where the ambient temperature is -15
to +30

(+5 to +86

), charge the UPS‘s battery every 6 months.

During extended storage in environments where the ambient temperature is
+30 to +45

(+86 to +113

), charge the UPS‘s battery every 3 months.

12. Specifications
__________________________________________________________
____

MODEL

325A

425A(P)

525A(P)

625A(P)

Capacity

325VA

425VA

525VA

625VA

Voltage

100V, 110V, 120V, 220V, 232V, 240V, +/-25%

INPUT

Frequency

50 or 60Hz +/-5% (auto sensing)

Voltage
(on battery)

Simulated sine wave at Line Input +/-5%

Frequency
(on battery)

50 or 60Hz +/-0.5%

Voltage
Regulation
AVR

AVR automatically increase output voltage 15% above input

voltage if -9% to-25% of nominal. AVR decrease output voltage

13% below input voltage if+9% to 25% of nominal

OUTPUT

Transfer Time

2/4 milliseconds, including detection time

Spike Protection

320 joules, 2ms

EMI/RFI filter

10dB at15MHz, 50dB at 30MHz

(for xxxAP models only)

Overload
Protection

UPS automatic shutdown if overload exceeds 110% of nominal at

60 second and 130% at 3 seconds.

Unit Input

Fuse for overload & short circuit protection

10Baase-T
Cable Port

Network (UTP, RJ-45) compatible jacks

(for xxxAp models only)

PROTECTION

and

FILTERING

Short Circuit

UPS output cut off immediately or input fuse protection

BATTERY

Type

Sealed, maintenance-free lead acid

Advertising
This manual is related to the following products: