N-Tron 702M12-W User Manual

Page 12

Advertising
background image

Revision 04062009

Page 12 of 52

APPLYING POWER (702-W Side View)


Unscrew & Remove the DC Voltage Input Plug from the Power Input Header
Install the DC Power Cables into the Plug (observing polarity).
Plug the Voltage Input Plug back into the Power Input Header.
Tightening torque for the terminal block power plug is 0.5 Nm/0.368 Pound Foot.
Verify the Power LED stays ON (GREEN).


Notes:

Only 1 power supply must be connected to power for minimal operation. For redundant power

operation, V

1

and V

2

inputs must be connected to separate DC Voltage sources. This device will

draw current from both sources simultaneously. Use 16-28 gauge wire when connecting to the
power supply.

The LAN port supports Power over Ethernet and can be used redundantly with the power input

mentioned above.


Recommended 24V DC Power Supplies, similar to: N-Tron’s P/N NTPS-24-1.3:

Input AC 115/230V
Output DC 24-28V
Output Current 1.3A @ 24V

1.0A @ 28V

Power 72W
35 mm DIN-Rail Mountable
Dimensions: 45X75X91 mm

Advertising