Applying power (top view) – N-Tron 710FX2 User Manual

Page 14

Advertising
background image

(Revised 2012-05-01

Page 14 of 170

APPLYING POWER (Top View)

Unscrew & Remove the DC Voltage Input
Plug from the Power Input Header

Install the DC Power Cables into the Plug
(observing polarity).

Plug the Voltage Input Plug back into the
Power Input Header.

Tightening torque for the terminal block
power plug is 0.5 Nm/0.368 Pound Foot.

Verify the Power LED stays ON (GREEN).



Notes:

Only 1 power supply must be connected to power for minimal operation. For redundant power
operation, V

1

and V

2

inputs must be connected to separate DC Voltage sources. This device will

draw current from both sources simultaneously. Use 16-28 gauge wire when connecting to the
power supply.

The Fault pins on the power connector can be used for an alarm contact. The current carrying
capacity is 1A at 24VDC. It is normally open and the relay closes when a fault condition occurs.
These pins can be used to connect an external warning device such as a light in order to provide an
external alarm. The conditions for generating a fault condition (closing the relay) can be configured
through software.




Recommended 24V DC Power Supplies, similar to: N-Tron’s P/N NTPS-24-1.3 (NOTE: Not appropriate
for use with M12, POE, and HV models.):

Input AC 115/230V

Output DC 24-28V

Output Current 1.3A @ 24V

1.0A @ 28V

Power 30W

35 mm DIN-Rail Mountable

Dimensions: 45X75X91 mm