Taking out of operation, Maintenance, Draining the tank – Nortec Industries GS Series User Manual

Page 16: Mandatory maintenance schedule

Advertising
background image

The vent terminal must be installed in the same

atmospheric pressure zone as the combustion air inlet
of the humidifier. If this is not possible (as in cases of
positive or negative room pressures) the humidifier
should be installed with the direct vent option.

ELECTRICAL

PRIMARY WIRING

All work concerning the electrical installation

must be performed by qualified personnel.

WARNING: The electrical parts inside the

humidifier are very sensitive to electrostatic discharge.
Appropriate measures against electrostatic discharge
(ESD protection) must be taken when carrying out
installation work.

· The humidifier should only be connected to

primary power (mains power) after all installation
work has been completed.

· An external disconnect switch must be installed

close to the unit to allow for power interruption
during servicing and/or maintenance.

· Humidifiers require field wiring to primary voltage

terminal blocks. Power requirement must be
120V or 208-240 Vac, 15A separately fused
circuit, single phase. Use only copper wire with a
minimum 70

°C (158 °F) temperature rating.

Wiring can be fed through a 7/8" hole on the
bottom or the top of the control compartment.
See Figure #1.

· When installed, the appliance must be electrically

grounded in accordance with local codes or, in
the absence of local codes, with the National
Electrical Code, ANSI/NFPA 70, and/or the CSA
C22.1 Electrical Code, if an external electrical
source is utilized.

· External wiring sizes must be in accordance with

NEC and/or CEC and existing local electrical
codes and by-laws.

LOW VOLTAGE CONTROL WIRING

All GS models require at least one type of input

control signal for unit operation. Refer to the sections
below that detail the types of controls that can be used
with each model.

Low voltage control terminal strips are provided in

the electrical compartment. Internal sides are factory
wired. External sides are to be field wired. Refer to
the specific control-wiring diagram supplied with each
unit.

Field wiring from humidistat to humidifier and

between devices should be shielded 18 AWG or
heavier and kept as short as possible.

Controls are available from NORTEC as

accessories and can be ordered with the humidifier.
Controls by others may also be used as long as they
meet the criteria noted below. The following is a
summary of the common types of controls that may be
used with NORTEC Gas Humidifiers.

Wall or Duct Mounted Control On/Off

Humidistat: Wired to make on drop in humidity,
break on rise to setpoint. Set to desired RH. Can
be a make/break set of contacts from a Building
Automation System.

Duct Mounted Safety High Limit On/Off

Humidistat: Wired to make on drop in humidity,
break on rise to safety setpoint. Set to
approximately 85% RH as a safety to prevent
saturation and wetting in the duct. Highly
recommended for ducted applications.

Duct Mounted Safety Air Proving On/Off Switch:

Wired to make when sensing air flow, break when no
air flow. Used as a safety to prevent saturation when
there is no air flow. Highly recommended for ducted
applications.

Wall or Duct Mounted Modulating Humidistat:

Provides a modulating signal to the unit that
represents the output (up to 100%) required from the
humidifier. Signal type can be changed in the field via
dip switch settings on the logic control board.

All GS models may be configured for either single

or dual channel modulation. Control signals can be
0-10 VDC or 0-20 mA (0-5 VDC, 1-5 VDC, 4-20 mA
and 2-10 VDC are also available). The unit must be
ordered from the factory for the desired signal type
and number of channels. When configured for
2-channel modulation the humidifier will generate
steam only if both channels indicate a demand. If both
channels are demanding steam the humidifier will
satisfy the lower demand signal.

- 12 -