Gas piping, Indoor installation, Locating and mounting – Nortec Industries GS Series User Manual

Page 8

Advertising
background image

INDOOR INSTALLATION

The installation must conform with local building

codes or, in the absence of local codes, with the ANSI
Z223.1, National Fuel Gas Code, and/or CAN/CGA
B149 Installation Codes. Refer to the Gas Piping
section of this manual.

LOCATING AND MOUNTING

GS Series humidifiers are designed for floor

mounting or on a GS Stand (optional). The clearance
dimensions shown in this manual are for reference
only and are the minimum required for maintenance of
the humidifier. Local and National Codes should be
consulted prior to final location and installation of the
humidifier. NORTEC cannot accept responsibility for
installation code violations.

Figure #1 shows a typical installation with all

required connections to the GS Humidifier. Careful
consideration should be given to all of these
connections when choosing a location for the
humidifier.

WARNING: During installation cover the
humidifier to prevent any dust or other
contaminants from entering the cabinets when
activities such as drilling are taking place.

· Ambient temperature location for humidifier:

41ºF - 104ºF (5ºC - 40ºC).

· Relative humidity location for humidifiers:

5% rh - 80% rh.

· All GS humidifiers are rated for the clearance to

shown in Figure #2.

· Location of the steam distributor should be

minimum of 36” above the humidifier.

· DO NOT locate humidifier any further than

absolutely necessary from steam distributor
location. Net output will be reduced as a result of
heat loss through steam line. Also, increased
static pressure (over 12" W.C.) will result in hot
water going down the drain. Consult factory if this
situation occurs.

· Where possible, mount humidifier at a height

convenient for servicing.

· Make sure the humidifier is mounted level.

· DO NOT mount humidifier on hot surfaces.

· The humidifier must be installed so that all

electrical components are protected from
exposure to water.

- 4 -

Optional Stand

Minimum

36" (91.5 cm)

Right

30" (76.2 cm)

Minimum

4" (10.2 cm) to vent pipe

Left

36" (91.5 cm)

Required only for

GSTC/GSP

500/600

Front

30" (76.2 cm)

Front Clearance

Side Clearance

Figure #2

Clearance Requirements