Pxi setup menu, Labview rt setup menu, Pxi setup menu -8 labview rt setup menu -8 – National Instruments PXI-8184 User Manual

Page 21

Advertising
background image

Chapter 2

Installation and Configuration

NI PXI-8184/8185 User Manual

2-8

ni.com

Port

section of Chapter 3,

I/O Information

, for pinout information.)

Setting this option to Parallel Port disables normal LPT1
functionality. The default is Disabled.

Legacy USB Support—Use this setting to use a USB keyboard and
mouse as if they were standard PS/2-style peripherals. You must enable
this setting to use these devices in operating systems with no USB
support and to boot from a USB floppy or CD-ROM. The BIOS setup
screen always works with USB keyboards regardless of this setting.
Certain real-time applications may require you to disable this setting
to reduce loop time jitter. The default is Enabled.

PXI Setup Menu

Use this menu to control and route certain signals on the PXI backplane.
Normally, you do not need to modify these settings. However, other
sections of this manual may indicate that modifications are necessary
and may lead to unpredictable behavior.

INTP Routing—You can route INTP to ISA IRQ 14, for use by a
PXI device functioning as a Primary IDE Controller. The default
setting is Not Routed.

INTS Routing—You can route INTS to ISA IRQ 15, for use by a
PXI device functioning as a Secondary IDE Controller. You also can
route it to the controller’s 21-frame serialized IRQ input, for use by
certain PXI carrier cards. The default setting is Not Routed.

Note

If INTS or INTP is routed to an ISA IRQ, you must disable one or both channels of

the integrated IDE/ATA controller for correct operation of this routing.

LabVIEW RT Setup Menu

Note

This menu is visible only if the controller supports LabVIEW RT.

Use this menu to configure boot options for LabVIEW RT if it is installed
on the controller. If you are not using LabVIEW RT, you should leave these
settings as default.

Note

These settings override the behavior of the switches on SW1. Refer to the

LabVIEW

RT Configuration Switches

section for more information. To use the settings from the

switches, select Use Hardware Switch for each option.