Table 3. NH System Messages (cont)

NHTC Display Message

LED state

System Action

Symptom Diagnosed

W27: Safety loop instability

YEL

The safety loop is interrupting
humidifier operation.

A security control is causing the safety
loop to switch on and off too rapidly.

W28: demand signal instability

YEL

The demand signal is swinging
from low demand to high
demand too quickly.

The demand signal is unstable.

W29: limit signal instability

YEL

The limit signal is swinging from
low demand to high demand too
quickly and the humidifier
cannot respond.

The limit signal is unstable.

W30: Modbus remote disable

YEL

The humidifier is being
controlled via the network, not
locally.

The humidifier has been disabled by a
network message.

W43: Keep warm active

YEL

This is a customer selectable
feature to keep the cylinder
water warm.

The humidifier is in standby mode.
The cylinder may energize at any
time.

W44: Demand signal short
cycling

YEL

The cylinder automatically
reduces the humidifier output to
stabilize operation.

The demand signal is cycling on and
off too frequently.

W45: safety loop short cycling

YEL

The cylinder automatically
reduces the humidifier output to
stabilize operation.

The demand signal is cycling on and
off too frequently.

W46: RH high warning

YEL

An alarm indication is
generated.

RH levels higher than the limit set
have been detected. The humidifier
should not be operational with this
warning activated.

W47: RH low warning

YEL

The humidifier is operating and
an alarm indication is
generated.

RH levels lower than the limit set have
been detected. The humidifier should
be operational with this warning
activated.

W49: wrong cylinder installed

YEL

An alarm indication is
generated.

The cylinder installed is not the
recognized type for the humidifier.

E50: Modbus Timeout

RED

Systems shuts down.

Time window for Modbus has elapsed.