Nortec NH Series User Manual

Page 80

Advertising
background image

10-50

Page 73
2008-08-28

D.

HUMIDIFIER MANDATORY START-UP CHECKLIST AND QUICK REFERENCE

Unit Serial #: _________________No. of humidifiers: _______ Tag: _______________
Unit type: ___________________Voltage: _____V/___ph

Steam output: ____lbs/hr

Customer/Job: ______________ Address: ______________________________________
Inspected by: ________________Date of inspection: ____/____/____

1.

PRELIMINARY:

– Pre-start-up checklist completed? yes

___

no

___

If no, return to Pre-Start-up Checklist before going on with start-up procedure.

2.

START-UP PROCEDURE:

The prerequisites for getting power and water into the steam cylinder are as follows:

– check that main breaker is on and power is at the unit.
– check that main water shut-off valve is open.
– on/off/drain switch must be switched on.
– control circuit 1-2 must be made.
– modulation humidistat, if present, must be calling.
– door interlock switch must be made (interlock switch can be pulled out to operate unit).

The unit will undergo a self-test to ensure integrity of all the components:

– NHTC Start-Up Unit Cylinder
– Reading Cylinder Data
– Inlet Valve
– Drain Valve
– Heat Controller
– Pump
– Bleed Valve
– Steam Relay
– Service Relay
– Error Relay
– Operation Relay

It will then start filling the cylinder and begins normal operation. Most water does not
contain enough conductivity for full boil on initial start-up. Units will need to concentrate
the water over a time period (hours to days).

Remarks: