Table b-2. ni 7831r i/o signal summary, E b-2, Ni 7831r i/o signal summary – National Instruments NI 7831R User Manual

Page 57: Ni 7831r i/o, Signal summary, Can damage, Connecting to compactrio extension i/o chassis

Advertising
background image

Appendix B

Connecting I/O Signals

NI 7831R User Manual

B-4

ni.com

Connecting to CompactRIO Extension I/O Chassis

You can use the CompactRIO R Series Expansion chassis and CompactRIO
I/O modules with the NI 7831R. Refer to the CompactRIO R Series
Expansion System Installation Instructions
for information about
connecting the chassis to the NI 7831R.

Table B-2. NI 7831R I/O Signal Summary

Signal Name

Signal

Type and
Direction

Impedance

Input/

Output

Protection

(Volts)

On/Off

Source

(mA at V)

Sink

(mA at V)

Rise Time

Bias

+5V

DO

AI<0..7>+

AI

10 G

Ω in

parallel with

100 pF

42/35

±

2 nA

AI<0..7>–

AI

10 G

Ω in

parallel with

100 pF

42/35

±

2 nA

AIGND

AO

AISENSE

AI

10 G

Ω in

parallel with

100 pF

42/35

±

2 nA

AO<0..7>

AO

1.25

Short-

circuit to

ground

2.5 at 10

2.5 at –10

10 V/µs

AOGND

AO

DGND

DO

DIO<0..15>
Connector 0

DIO<0..39>
Connector <1..2>

DIO

–0.5

to +7.0

5.0 at 2.4

5.0 at 0.4

12 ns

AI = Analog Input

AO = Analog Output

DIO = Digital Input/Output

DO = Digital Output

Advertising