Specifications, Installation, Input characteristics – National Instruments FP-PS-4 User Manual

Page 8: Output characteristics

Advertising
background image

FP-PS-4 Operating Instructions

8

ni.com

6. Connect the green or green/yellow conductor into the ground

terminal.

Caution

When you install the conductors, make sure that

the entire conductor is in the screw terminal and that there
are no loose strands outside of the terminal. Only install
one wire in each terminal.

Specifications

The following specifications are typical for a range of 0 to 60 °C,
unless otherwise noted.

Installation

Terminal wiring ................................ 16-26 AWG copper

conductor wire with 7 mm
(0.275 in.) strip length as
shown in Figure 8

Figure 8. Conductor Wire with the Correct Strip Length (drawing is to scale)

Torque for screw terminals ............... 0.5-0.6 Nm (4.4–5.3 in.-lbs)

Input Characteristics

Input voltage ..................................... 90–264 VAC

Frequency ......................................... 47–63 Hz, single phase

Maximum current consumption........ 0.6 A at 120 VAC, 60 Hz

Input protection................................. Nonreplaceable internal

AC fuse

Output Characteristics

Output voltage .................................. 24 VDC, nonadjusting

Nominal current (I

N

) ......................... 600 mA

Nominal continuous power

0 to 50 °C ................................... 15 W
50 to 60 °C ................................. 10 W

7 mm

Advertising