Table 4. Humidifier Variable Addresses

Unit #1

NHTC LINKS 2 Variable Listing

Default BACnet/IP Address: 192.168.10.11; Subnet: 255.255.255.0
Default BACnet/MSTP Address: 78

Default Johnson N2 Address: 174

Unit #1

BACnet

Lonworks

N2

Variable Name

Type Instance

SNVT

SNVT #

NV Index

Type

Instance

nvoHourOpt_1 AV

1

time_hour

124

1 AI 1

nvoCapLimit_1 AV

2

lev_percent

81 2 AI 2

nvoRHDem1_1 AV

3

lev_percent

81 3 AI 3

nvoSet1_1 AV

4

lev_percent

81

4

AI

4

nvoRHDem2_1 AV

5

lev_percent

81 5 AI 5

nvoSet2_1 AV

6

lev_percent

81

6

AI

6

nvoSysDemand_1 AV 7 lev_percent 81

7

AI

7

nviCapLimit_1 AV

8

lev_percent

81

8 AO 8

nviSet1_1 AV

9

lev_percent

81

9

AO

9

nviSet2_1 AV

10

lev_percent

81

10

AO

10

nviRHDem1_1 AV

11

lev_percent

81

11 AO 11

nviRHDem2_1 AV

12

lev_percent

81

12 AO 12

nviDisable_1 AV

13

switch

95

20

AO

13

Expansion_1 AV

14

N/A

N/A

N/A

AO

14

Expansion_1 AV

15

N/A

N/A

N/A

AO

15

nvoFault_1 BV

1

switch

95

13

Binary

In

1

nvoHWSensor_1 BV 2 switch 95 14 Binary

In 2

nvoNetSensor BV

3

switch

95

15

Binary

In

3

nvoDisable_1 BV

4

switch

95

16

Binary

In

4

nvoSecurity_1 BV

5

switch

95

17

Binary

In

5

nvoService_1 BV

6

switch

95

18

Binary

In

6

nvoStatus_1 BV

7

switch

95

19

Binary

In

7

Expansion_1 BV

8

N/A

N/A

N/A

Binary

Out

8

nviNetSensor_1 BV

9 switch 95 21

Binary

Out

9

nvoConnection_1 BV 10 switch 95 22 Binary

Out

10

Expansion_1 BV

11

N/A

N/A

N/A

Binary

Out

11

Expansion_1 BV

12

N/A

N/A

N/A

Binary

Out

12

Expansion_1 BV

13

N/A

N/A

N/A

Binary

Out

13

Expansion_1 BV

14

N/A

N/A

N/A

Binary

Out

14

Expansion_1 BV

15

N/A

N/A

N/A

Binary

Out

15