Dv_lo_lim (alarming), Dv_lo_pri (alarming), Fault_state (faultstate, option) – National Instruments NI-FBUS User Manual

Page 82: Feature_sel/features (diagnostic, option), Table 4-12. feature parameter options

Advertising
background image

Chapter 4

Parameters

© National Instruments Corporation

4-17

NI-FBUS Configurator User Manual

DV_LO_LIM (Alarming)

The deviation limit between the PID block setpoint and process value,
in engineering units, beyond which the deviation low alarm is considered
active.

DV_LO_PRI (Alarming)

The priority of the deviation low alarm.

FAULT_STATE (Faultstate, Option)

The current status of the device faultstate. It can be set and cleared with

SET_FSTATE

and

CLR_FSTATE

. If it is set, all output blocks in the device

initiate their own faultstate behavior.

FEATURE_SEL/FEATURES (Diagnostic, Option)

The

FEATURES

parameter lists features supported by the device. Use the

FEATURE_SEL

parameter to manually enable and disable the supported

features listed in the

FEATURES

parameter.

Table 4-12. Feature Parameter Options

Option

Description

Unicode

The device supports strings in

Unicode

format. The FP-3000 does

not support this feature.

Reports

The device supports event report messages for alarming. If this
feature is not selected in the

FEATURE_SEL

parameter, the

FP-3000 continues to detect alarms and events, but does not report
them over the bus. In this case, the host must poll the alarm
parameters to detect alarm conditions as they change.

Faultstate

The device supports

Faultstate

behavior for output blocks.

Soft Write Lock

The device supports locking of configuration of parameters with
the

WRITE_LOCK

parameter in the resource block. With this

feature selected and the

WRITE_LOCK

parameter written to

Set

,

writes to all static configuration parameters are disallowed.

Hard Write Lock

The device supports locking of configuration parameters. For the
FP-3000, a switch on the back of the device must also be set.
If

Hard Write Lock

is enabled, the switch disallows writes to all

configuration parameters in the device, including

FEATURE_SEL

.

Advertising