Nortec MH Series User Manual
Page 24
10-10
Page 20
2008-12-03
1.1.12
Performing remote relay tests
With the test functions under “Remote Test” you can check the function of the relays
“Humidification”, “Service”, “Error” and “Unit on”.
Select “Remote Test” in the settings menu,
then press the <Set> key.
Press the <
Ç> and <È>
keys in order to select the relay you want to
test and press the <Set> key to
activate/deactivate the corresponding relay for
testing.
1.1.13
Setting the date
Select “Date” in the settings menu, then press
the <Set> key. In the following dialogue set the
actual date (format “tt.mm.jj”).
1.1.14
Setting the time
Select “Time” in the settings menu, then press
the <Set> key. In the following dialogue set the
actual time (format “hh.mm”).
1.1.15
Setting the display contrast
Select “Contrast” in the settings menu, then
press the <Set> key. In the following dialogue
set the desired value for the display contrast.
Factory setting: 20
Setting range: 0 (no display) ...100 (display
turns black).