No signal from
conductivity sensor

No signal from
conductivity sensor

Red
flashes

Red
lights

Sensor cable not
connected or
sensor cable
interrupted.

Connect/replace
sensor cable.

Conductivity
transmitter
defective or wrong
version
(conductivity
constant).

Replace
conductivity
transmitter.

Conductivity
transmitter not
configured
correctly.

Contact your
Nortec supplier.

Conductivity sensor
defective.

Replace
conductivity
sensor.

Nortec SH2 deactivated
via Modbus

Modbus system failed

Red
flashes

Red
lights

Nortec MH
deactivated via
Modbus.

None or activate
Nortec MH via
Modbus.

Modbus system
failed.

Check/activate
Modbus system.

Timeout Modbus

Red
flashes

-- Red

lights

Timeout. No
activity from
Modbus

Activate Modbus
system

Cleaning of humidification
boxes in progress

--

-- --

Cleaning

of

humidification
boxes in progress.

None (wait).

Draining of water tub in
progress

--

-- --

Draining

of

water

tub in progress.

None (wait).