Wiring a Power Vent Assembly

to an Appliance with IID

Ignition

Venting

The vent pipe must be the same size or one size larg-

er than what is indicated. The D-2 Power Vent is

capable of 360-degree discharge rotation and oper-

ates with a positive vent static pressure and with a

vent gas temperature less than 400°F. The total

length of horizontal run shall not exceed an equiv-

alent of 40 feet including termination cap. For all

cases, each 90-degree elbow reduces the maximum

horizontal vent run by 10 feet and each 45-degree

elbow in the vent run reduces the maximum vent run

by 5 feet. See the table below for maximum vent

lengths using 90-degree and 45-degree elbows.

The D-2 Power Vent uses positive pressure to push

flue gases through the vent pipe to the outside. The

vent must be installed to prevent flue gas leakage.

Care must be taken during assembly to ensure that all

joints are sealed properly and are airtight.

The vent must be installed to prevent the potential

accumulation of condensate in the vent pipes. It is rec-

ommended that:

a) The vent be installed with a slight downward slope

of not more than 1/4” per foot of horizontal run to the

vent terminal.

b) The vent be insulated through the length of horizon-

tal run.

For appliances installed in extreme cold climate, it is

recommended that:

a) The vent be installed with a slight upward slope of

not more than 1/4” per foot of horizontal run to the vent

terminal. In this case, an approved condensate trap

must be installed per applicable codes.

b) The vent be insulated through the length of the hor-

izontal run.

Fig. 4: Draft Assembly

The Raypak Power Vent operates with a positive vent

static pressure and with a vent gas temperature that

avoids excessive condensate production in the vent

and as such it is listed as a CATEGORY III appliance.

Exception: When a Power Vent is connected to a ver-

tical vent of sufficient height to generate a negative

draft in the system. Consult sizing guide or factory.

The D-2 Power Vent assembly is suitable for through

the wall venting, and for connection to smaller size

vent pipes and breeching other than the standard

atmospheric heater.

WARNING: Disconnect all electrical power to the

unit before servicing to avoid potential shock injury

or damage to the unit. To change voltages, follow

wiring diagram for correct voltage connections.

Improper wiring connections can burnout the relay

and blower motor.

90 Degree Elbows

45 Degree Elbows

Quantity

Maximum

Length (ft)

Quantity

Maximum

Length (ft)

1

30

1

35

2

20

2

30

3

10

3

25

Table C: Reduced Maximum Equivalent Vent Run