Systems performance—rsna-b series, Gross systems performance data—rsna-b024, Gross systems performance data—rsna-b030 – Rheem RSNA-B Series User Manual

Page 11

Advertising
background image

11

SYSTEMS PERFORMANCE—RSNA-B SERIES

GROSS SYSTEMS PERFORMANCE DATA—RSNA-B024

ENTERING INDOOR AIR @ 80°F [26.7°C] dbE

wbE

71°F [21.7°C]

67°F [19.4°C]

63°F [17.2°C]

CFM [L/s]

880 [415]

800 [378]

680 [321]

880 [415]

800 [378]

680 [321]

880 [415]

800 [378]

680 [321]

DR

.21

.20

.18

.21

.20

.18

.21

.20

.18

O
U

T

D
O
O
R

D
R
Y

B
U

L

B

T
E

M

P
E
R
A
T
U
R
E

°F

[°C]

75

[23.9]

Total BTUH [kW]
Sens BTUH [kW]
Power

28.9 [8.47]
16.2 [4.75]

1.4

28.4 [8.32]
15.4 [4.51]

1.3

27.6 [8.09]
14.4 [4.22]

1.3

27.3 [8.00]
19.5 [5.71]

1.3

26.8 [7.85]
18.6 [5.45]

1.3

26.1 [7.65]
17.3 [5.07]

1.3

25.0 [7.33]
22.0 [6.45]

1.3

24.6 [7.21]
21.1 [6.18]

1.3

23.9 [7.00]
19.6 [5.74]

1.3

80

[26.7]

Total BTUH [kW]
Sens BTUH [kW]
Power

28.9 [8.47]
16.1 [4.72]

1.5

28.4 [8.32]
15.4 [4.51]

1.5

27.6 [8.09]
14.3 [4.19]

1.4

27.2 [7.97]
19.5 [5.71]

1.5

26.8 [7.85]
18.6 [5.45]

1.4

26.0 [7.62]
17.3 [5.07]

1.4

25.0 [7.33]
22.0 [6.45]

1.4

24.5 [7.18]
21.0 [6.15]

1.4

23.9 [7.00]
19.6 [5.74]

1.4

85

[29.4]

Total BTUH [kW]
Sens BTUH [kW]
Power

28.5 [8.35]
16.0 [4.69]

1.6

28.0 [8.21]
15.3 [4.48]

1.6

27.2 [7.97]
14.2 [4.16]

1.5

26.9 [7.88]
19.3 [5.66]

1.6

26.4 [7.74]
18.5 [5.42]

1.6

25.7 [7.53]
17.2 [5.04]

1.5

24.6 [7.21]
21.9 [6.42]

1.5

24.1 [7.06]
20.9 [6.13]

1.5

23.5 [6.89]
19.5 [5.71]

1.5

90

[32.2]

Total BTUH [kW]
Sens BTUH [kW]
Power

27.8 [8.15]
15.8 [4.63]

1.7

27.3 [8.00]
15.1 [4.43]

1.7

26.6 [7.80]
14.0 [4.10]

1.7

26.2 [7.68]
19.1 [5.60]

1.7

25.7 [7.53]
18.3 [5.36]

1.7

25.0 [7.33]
17.0 [4.98]

1.7

23.9 [7.00]
21.7 [6.36]

1.6

23.5 [6.89]
20.7 [6.07]

1.6

22.8 [6.68]
19.3 [5.66]

1.6

95

[35]

Total BTUH [kW]
Sens BTUH [kW]
Power

27.0 [7.91]
15.5 [4.54]

1.8

26.5 [7.77]
14.8 [4.34]

1.8

25.8 [7.56]
13.8 [4.04]

1.8

25.3 [7.41]
18.9 [5.54]

1.8

24.8 [7.27]
18.0 [5.28]

1.8

24.2 [7.09]
16.8 [4.92]

1.8

23.0 [6.74]
21.4 [6.27]

1.8

22.6 [6.62]
20.5 [6.01]

1.7

22.0 [6.45]
19.0 [5.57]

1.7

100

[37.8]

Total BTUH [kW]
Sens BTUH [kW]
Power

26.0 [7.62]
15.2 [4.45]

1.9

25.5 [7.47]
14.5 [4.25]

1.9

24.8 [7.27]
13.5 [3.96]

1.9

24.3 [7.12]
18.5 [5.42]

1.9

23.9 [7.00]
17.7 [5.19]

1.9

23.2 [6.80]
16.4 [4.81]

1.9

22.1 [6.48]
21.1 [6.18]

1.9

21.7 [6.36]
20.1 [5.89]

1.9

21.1 [6.18]
18.7 [5.48]

1.8

105

[40.6]

Total BTUH [kW]
Sens BTUH [kW]
Power

25.0 [7.33]
14.7 [4.31]

2.0

24.5 [7.18]
14.1 [4.13]

2.0

23.9 [7.00]
13.1 [3.84]

2.0

23.3 [6.83]
18.1 [5.30]

2.0

22.9 [6.71]
17.3 [5.07]

2.0

22.3 [6.54]
16.1 [4.72]

2.0

21.1 [6.18]
20.6 [6.04]

2.0

20.7 [6.07]
19.7 [5.77]

2.0

20.1 [5.89]
18.3 [5.36]

1.9

110

[43.3]

Total BTUH [kW]
Sens BTUH [kW]
Power

24.1 [7.06]
14.3 [4.19]

2.1

23.7 [6.95]
13.6 [3.99]

2.1

23.0 [6.74]
12.7 [3.72]

2.1

22.4 [6.56]
17.6 [5.16]

2.1

22.0 [6.45]
16.8 [4.92]

2.1

21.4 [6.27]
15.6 [4.57]

2.1

20.2 [5.92]
20.1 [5.89]

2.1

19.8 [5.80]
19.2 [5.63]

2.1

19.3 [5.66]
17.9 [5.25]

2.1

115

[46.1]

Total BTUH [kW]
Sens BTUH [kW]
Power

23.3 [6.83]
13.7 [4.02]

2.3

22.9 [6.71]
13.1 [3.84]

2.2

22.3 [6.54]
12.2 [3.58]

2.2

21.7 [6.36]
17.0 [4.98]

2.3

21.3 [6.24]
16.3 [4.78]

2.2

20.7 [6.07]
15.1 [4.43]

2.2

19.4 [5.69]
19.4 [5.69]

2.2

19.1 [5.60]
18.7 [5.48]

2.2

18.5 [5.42]
17.4 [5.10]

2.2

GROSS SYSTEMS PERFORMANCE DATA—RSNA-B030

ENTERING INDOOR AIR @ 80°F [26.7°C] dbE

wbE

71°F [21.7°C]

67°F [19.4°C]

63°F [17.2°C]

CFM [L/s]

1100 [519]

1000 [472]

850 [401]

1100 [519]

1000 [472]

850 [401]

1100 [519]

1000 [472]

850 [401]

DR

.24

.23

.21

.24

.23

.21

.24

.23

.21

O
U

T

D
O
O
R

D
R
Y

B
U

L

B

T
E

M

P
E
R
A
T
U
R
E

°F

[°C]

75

[23.9]

Total BTUH [kW]
Sens BTUH [kW]
Power

37.6 [11.02]
21.3 [6.24]

1.9

36.9 [10.81]
20.3 [5.95]

1.9

35.9 [10.52]
18.9 [5.54]

1.9

35.0 [10.26]
25.2 [7.39]

1.9

34.4 [10.08]
24.1 [7.06]

1.9

33.4 [9.79]
22.4 [6.56]

1.9

33.6 [9.85]
27.2 [7.97]

1.9

33.0 [9.67]
26.0 [7.62]

1.9

32.1 [9.41]
24.2 [7.09]

1.9

80

[26.7]

Total BTUH [kW]
Sens BTUH [kW]
Power

37.1 [10.87]
20.8 [6.10]

2.1

36.4 [10.67]
19.9 [5.83]

2.0

35.4 [10.37]
18.5 [5.42]

2.0

34.5 [10.11]
24.7 [7.24]

2.0

33.9 [9.94]
23.6 [6.92]

2.0

32.9 [9.64]
22.0 [6.45]

2.0

33.1 [9.70]
26.7 [7.83]

2.0

32.5 [9.52]
25.5 [7.47]

2.0

31.6 [9.26]
23.8 [6.98]

2.0

85

[29.4]

Total BTUH [kW]
Sens BTUH [kW]
Power

36.3 [10.64]
20.3 [5.95]

2.2

35.6 [10.43]
19.4 [5.69]

2.2

34.7 [10.17]
18.0 [5.28]

2.1

33.7 [9.88]
24.2 [7.09]

2.2

33.1 [9.70]
23.1 [6.77]

2.1

32.2 [9.44]
21.5 [6.30]

2.1

32.3 [9.47]
26.2 [7.68]

2.1

31.7 [9.29]
25.1 [7.36]

2.1

30.9 [9.06]
23.3 [6.83]

2.1

90

[32.2]

Total BTUH [kW]
Sens BTUH [kW]
Power

35.3 [10.35]
19.8 [5.80]

2.3

34.7 [10.17]
18.9 [5.54]

2.3

33.8 [9.91]
17.6 [5.16]

2.2

32.8 [9.61]
23.7 [6.95]

2.3

32.2 [9.44]
22.6 [6.62]

2.2

31.3 [9.17]
21.1 [6.18]

2.2

31.4 [9.20]
25.7 [7.53]

2.3

30.8 [9.03]
24.6 [7.21]

2.2

30.0 [8.79]
22.9 [6.71]

2.2

95

[35]

Total BTUH [kW]
Sens BTUH [kW]
Power

34.3 [10.05]
19.3 [5.66]

2.4

33.7 [9.88]
18.4 [5.39]

2.4

32.8 [9.61]
17.1 [5.01]

2.4

31.7 [9.29]
23.2 [6.80]

2.4

31.2 [9.14]
22.1 [6.48]

2.4

30.3 [8.88]
20.6 [6.04]

2.3

30.3 [8.88]
25.2 [7.39]

2.4

29.8 [8.73]
24.1 [7.06]

2.4

29.0 [8.50]
22.4 [6.56]

2.3

100

[37.8]

Total BTUH [kW]
Sens BTUH [kW]
Power

33.2 [9.73]
18.7 [5.48]

2.5

32.6 [9.55]
17.9 [5.25]

2.5

31.7 [9.29]
16.6 [4.86]

2.5

30.6 [8.97]
22.7 [6.65]

2.5

30.1 [8.82]
21.6 [6.33]

2.5

29.3 [8.59]
20.1 [5.89]

2.4

29.2 [8.56]
24.7 [7.24]

2.5

28.7 [8.41]
23.6 [6.92]

2.5

27.9 [8.18]
21.9 [6.42]

2.4

105

[40.6]

Total BTUH [kW]
Sens BTUH [kW]
Power

32.1 [9.41]
18.2 [5.33]

2.6

31.6 [9.26]
17.4 [5.10]

2.6

30.7 [9.00]
16.2 [4.75]

2.6

29.6 [8.67]
22.1 [6.48]

2.6

29.0 [8.50]
21.2 [6.21]

2.6

28.3 [8.29]
19.7 [5.77]

2.6

28.2 [8.26]
24.2 [7.09]

2.6

27.7 [8.12]
23.1 [6.77]

2.6

26.9 [7.88]
21.5 [6.30]

2.5

110

[43.3]

Total BTUH [kW]
Sens BTUH [kW]
Power

31.2 [9.14]
17.7 [5.19]

2.7

30.6 [8.97]
16.9 [4.95]

2.7

29.8 [8.73]
15.7 [4.60]

2.7

28.6 [8.38]
21.6 [6.33]

2.7

28.1 [8.24]
20.7 [6.07]

2.7

27.3 [8.00]
19.2 [5.63]

2.7

27.2 [7.97]
23.7 [6.95]

2.7

26.7 [7.83]
22.6 [6.62]

2.7

26.0 [7.62]
21.0 [6.15]

2.7

115

[46.1]

Total BTUH [kW]
Sens BTUH [kW]
Power

30.4 [8.91]
17.2 [5.04]

2.9

29.8 [8.73]
16.5 [4.84]

2.8

29.0 [8.50]
15.3 [4.48]

2.8

27.8 [8.15]
21.1 [6.18]

2.8

27.3 [8.00]
20.2 [5.92]

2.8

26.6 [7.80]
18.8 [5.51]

2.8

26.4 [7.74]
23.2 [6.80]

2.8

25.9 [7.59]
22.1 [6.48]

2.8

25.2 [7.39]
20.6 [6.04]

2.8

DR —Depression ratio
dbE —Entering air dry bulb
wbE—Entering air wet bulb

Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power—KW input

NOTES:

➀ When the entering air dry bulb is other than 80°F [27°C], adjust the sensible

capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].

[

] Designates Metric Conversions

Advertising