CONNECTIONS – ELECTRICAL

30

POWER FLUE EXTERNAL CONTROLS – INTERMITTENT OPERATION



INTERLOCK TERMINAL

621 SERIES RHEEM

multiple water heater installation

Notes
1. Power source for the water heater, fan and

control circuit must be from the same circuit.

2. R1 monitors return signal.
3. R2 monitors alarm signal.
4. T1 to be set for 20-30 seconds.
5. Meets requirements of Clause H.2.2.6 of

AS5601 – 2004, providing lockout in the event of
flue product flow failure.

6. Where intermittent fan operation is utilised, it is

necessary to run the fan for some time after
combustion ceases to prevent flue spillage of
combustion products. T2 to be set for 5 minutes.

jumper lead must be removed

for connection to a power flue

For a single water heater

installation, connect 1 and 2

directly to the water heater

2

1

2

2

2

1

1

1