7

Tables C: Air Turnover Cooling Unit with Filtration Performance Information

Tables B: Air Turnover Heating Unit with Filtration Performance Information

(Additional configurations are available upon request.)

AT-136

CFM

Motor (HP)

Output

(MBH)

Minimum

Output

(MBH)

Maximum

Temp. Rise

Range (°F)

Base Unit

Weight

(lbs.)

4,500

1 (1 motor)

240

450

49 to 93

2,425

9,000

3 (1 motor)

240

450

25 to 46

2,505

12,000 5 (1 motor)

240

450

19 to 35

2,520

AT-148

CFM

Motor (HP)

Output

(MBH)

Minimum

Output

(MBH)

Maximum

Temp. Rise

Range (°F)

Base Unit

Weight

(lbs.)

10,000 3 (1 motor)

240

450

22 to 42

3,455

16,000 5 (1 motor)

240

750

14 to 43

3,470

AT-154

CFM

Motor (HP)

Output

(MBH)

Minimum

Output

(MBH)

Maximum

Temp. Rise

Range (°F)

Base Unit

Weight

(lbs.)

14,000 3 (1 motor)

240

450

16 to 30

4,080

22,000 5 (1 motor)

240

750

10 to 32

4,140

30,000 10 (1 motor)

520

1,000

16 to 31

4,210

30,000 10 (1 motor)

560

1,250

17 to 39

4,420

AT-236

CFM

Motor (HP)

Output

(MBH)

Minimum

Output

(MBH)

Maximum

Temp. Rise

Range (°F)

Base Unit

Weight

(lbs.)

9,000 1 (2 motors)

240

450

25 to 46

4,145

18,000 3 (2 motors)

240

750

12 to 39

4,240

24,000 5 (2 motors)

520

1,000

20 to 39

4,270

AT-242

CFM

Motor (HP)

Output

(MBH)

Minimum

Output

(MBH)

Maximum

Temp. Rise

Range (°F)

Base Unit

Weight

(lbs.)

21,000 3 (2 motors)

240

750

11 to 33

5,240

31,000 5 (2 motors)

520

1,000

16 to 30

5,270

31,000 5 (2 motors)

560

1,250

17 to 37

5,445

AT-248

CFM

Motor (HP)

Output

(MBH)

Minimum

Output

(MBH)

Maximum

Temp. Rise

Range (°F)

Base Unit

Weight

(lbs.)

22,000 3 (2 motors)

240

750

10 to 32

6,190

35,000 5 (2 motors)

520

1,000

14 to 26

6,345

45,000 7.5 (2 motors)

560

1,250

12 to 26

6,575

45,000 7.5 (2 motors)

560

1,500

12 to 31

6,730

AT-254

CFM

Motor (HP)

Output

(MBH)

Minimum

Output

(MBH)

Maximum

Temp. Rise

Range (°F)

Base Unit

Weight

(lbs.)

40,000 5 (2 motors)

560

1,750

13 to 41

7,870

60,000 10 (2 motors)

600

2,250

9 to 35

8,310

65,000 10 (2 motors)

600

2,500

9 to 36

8,560

AT-260

CFM

Motor (HP)

Output

(MBH)

Minimum

Output

(MBH)

Maximum

Temp. Rise

Range (°F)

Base Unit

Weight

(lbs.)

54,000 5 (2 motors)

600

3,000

10 to 51

11,070

61,000 7.5 (2 motors)

720

4,000

11 to 61

11,335

74,000 10 (2 motors)

720

4,000

9 to 50

11,385

AT-272

CFM

Motor (HP)

Output

(MBH)

Minimum

Output

(MBH)

Maximum

Temp. Rise

Range (°F)

Base Unit

Weight

(lbs.)

62,000

7.5 (2 mo-

tors)

600

3,000

9 to 45

12,160

88,000 10 (2 motors)

720

4,500

8 to 47

12,385

100,000 15 (2 motors)

720

4,500

7 to 42

12,515

AT-136

CFM

Motor (HP)

Base Unit Weight (lbs.)

4,500

1 (1 motor)

2,425

9,000

3 (1 motor)

2,505

12,000

5 (1 motor)

2,520

AT-148

CFM

Motor (HP)

Base Unit Weight (lbs.)

10,000

3 (1 motor)

3,455

16,000

5 (1 motor)

3,470

AT-154

CFM

Motor (HP)

Base Unit Weight (lbs.)

14,000

5 (1 motor)

4,080

22,000

5 (1 motor)

4,140

30,000

10 (1 motor)

4,210

30,000

10 (1 motor)

4,420

AT-236

CFM

Motor (HP)

Base Unit Weight (lbs.)

9,000

2 (1 motors)

4,145

18,000

3 (2 motors)

4,240

24,000

5 (2 motors)

4,270

AT-242

CFM

Motor (HP)

Base Unit Weight (lbs.)

21,000

3 (2 motors)

5,240

31,000

5 (3 motors)

5,270

31,000

5 (3 motors)

5,445

AT-248

CFM

Motor (HP)

Base Unit Weight (lbs.)

22,000

3 (2 motors)

6,190

35,000

5 (2 motors)

6,345

45,000

7.5 (2 motors)

6,575

45,000

7.5 (2 motors)

6,730

AT-254

CFM

Motor (HP)

Base Unit Weight (lbs.)

40,000

5 (2 motors)

7,870

60,000

10 (2 motors)

8,310

65,000

10 (2 motors)

8,560

AT-260

CFM

Motor (HP)

Base Unit Weight (lbs.)

54,000

5 (2 motors)

11,070

61,000

7.5 (2 motors)

11,335

74,000

10 (2 motors)

11,385

AT-272

CFM

Motor (HP)

Base Unit Weight (lbs.)

62,000

7.5 (2 motors)

12,160

88,000

10 (2 motors)

12,385

100,000

15 (2 motors)

12,515

(For cooling applications, consult factory. Base Unit Weights do not account for inclusion of cooling coils or exclusion of heat exchanger.