Roberts Gorden Combat AT-236 User Manual

Page 8

Advertising
background image

Printed in U.S.A.

CATDSGNA

2M 1107 Orig

Tables D: Air Turnover Heating/Cooling Unit with Filtration Performance Information

AT-136

CFM

Motor (HP)

Output

(MBH)

Minimum

Output

(MBH)

Maximum

Temp. Rise

Range (°F)

Base Unit

Weight

(lbs.)

4,500

1.5 (1 motor)

240

450

49 to 93

2,425

9,000

5 (1 motor)

240

450

25 to 46

2,505

12,000

5 (1 motor)

240

450

19 to 35

2,520

AT-148

CFM

Motor (HP)

Output

(MBH)

Minimum

Output

(MBH)

Maximum

Temp. Rise

Range (°F)

Base Unit

Weight

(lbs.)

10,000

5 (1 motor)

240

450

22 to 42

3,455

16,000 7.5 (1 motor)

240

750

14 to 43

3,470

AT-154

CFM

Motor (HP)

Output

(MBH)

Minimum

Output

(MBH)

Maximum

Temp. Rise

Range (°F)

Base Unit

Weight

(lbs.)

14,000

5 (1 motor)

240

450

16 to 30

4,080

22,000 7.5 (1 motor)

240

750

10 to 32

4,140

30,000 10 (1 motor)

520

1,000

16 to 31

4,210

30,000 10 (1 motor)

560

1,250

17 to 39

4,420

AT-236

CFM

Motor (HP)

Output

(MBH)

Minimum

Output

(MBH)

Maximum

Temp. Rise

Range (°F)

Base Unit

Weight

(lbs.)

9,000 1.5 (2 motors)

240

450

25 to 46

4,145

18,000 5 (2 motors)

240

750

12 to 39

4,240

24,000 5 (2 motors)

520

1,000

20 to 39

4,270

AT-242

CFM

Motor (HP)

Output

(MBH)

Minimum

Output

(MBH)

Maximum

Temp. Rise

Range (°F)

Base Unit

Weight

(lbs.)

21,000 5 (2 motors)

240

750

11 to 33

5,240

31,000 7.5 (2 motors)

520

1,000

16 to 30

5,270

31,000 7.5 (2 motors)

560

1,250

17 to 37

5,445

AT-248

CFM

Motor (HP)

Output

(MBH)

Minimum

Output

(MBH)

Maximum

Temp. Rise

Range (°F)

Base Unit

Weight

(lbs.)

22,000 5 (2 motors)

240

750

10 to 32

6,190

35,000 7.5 (2 motors)

520

1,000

14 to 26

6,345

45,000 10 (2 motors)

560

1,250

12 to 26

6,575

45,000 10 (2 motors)

560

1,500

12 to 31

6,730

AT-254

CFM

Motor (HP)

Output

(MBH)

Minimum

Output

(MBH)

Maximum

Temp. Rise

Range (°F)

Base Unit

Weight

(lbs.)

40,000 5 (2 motors)

560

1,750

13 to 41

7,870

60,000 10 (2 motors)

600

2,250

9 to 35

8,310

65,000 15 (2 motors)

600

2,500

9 to 36

8,560

AT-260

CFM

Motor (HP)

Output

(MBH)

Minimum

Output

(MBH)

Maximum

Temp. Rise

Range (°F)

Base Unit

Weight

(lbs.)

54,000 7.5 (2 motors)

600

3,000

10 to 51

11,070

61,000 10 (2 motors)

720

4,000

11 to 61

11,335

74,000 15 (2 motors)

720

4,000

9 to 50

11,385

AT-272

CFM

Motor (HP)

Output

(MBH)

Minimum

Output

(MBH)

Maximum

Temp. Rise

Range (°F)

Base Unit

Weight

(lbs.)

62,000 7.5 (2 motors)

600

3,000

9 to 45

12,160

88,000 15 (2 motors)

720

4,500

8 to 47

12,385

100,000 15 (2 motors)

720

4,500

7 to 42

12,515

Roberts-Gordon, LLC

1250 William Street

P.O. Box 44

Buffalo, NY 14240-0044 USA

Telephone: 716.852.4400

Fax: 716.852.0854

Toll Free: 800.828.7450

www.rg-inc.com

European Office:

Roberts Gordon Europe Limited

Telephone: +44(0)121 506 7700

Fax: +44(0)121 506 7701

Installation Code and Annual Inspections:

All installations and service of ROBERTS GORDON

®

equipment must be performed by a contractor qualified in the installation and ser-

vice of equipment sold and supplied by Roberts-Gordon and conform to all requirements set forth in the ROBERTS GORDON

®

manuals

and all applicable governmental authorities pertaining to the installation, service and operation of the equipment. To help facilitate

optimum performance and safety, Roberts-Gordon recommends that a qualified contractor annually inspect your ROBERTS GORDON

®

equipment and perform service where necessary, using only replacement parts sold and supplied by Roberts-Gordon.

Further Information:

Applications, engineering and detailed guidance on systems design, installation and equipment performance is

available through ROBERTS GORDON

®

representatives. Please contact us for any further information you may require, including the

Installation, Operation and Service Manual.
This product is not for residential use.
This document is intended to assist licensed professionals in the exercise of their professional judgement.

© 2007 Roberts-Gordon, LLC All rights reserved. No part of this work covered by the copyrights herein may be reproduced or copied in any form

or by any means – graphic, electronic, or mechanical, including photocopying, recording, taping, or information

storage and retrieval systems – without written permission of Roberts-Gordon, LLC.

(For cooling applications, consult factory. Base Unit Weights do not account for inclusion of cooling coils or exclusion of heat exchanger.
Additional configurations are available upon request.)