SECTION 10: WIRING

Heaters can be controlled using several methods.
Normally thermostats are used to control the heaters
but they can also be controlled by an Energy

Management System.

Section 10.1 below illustrates

the connection for heaters controlled by a line voltage
thermostat. NOTE: In order to use line voltage ther-
mostats, the low voltage terminal located at the back
of each burner must be connected as shown in the
detail. For a single heater on a low voltage thermo-
stat,

See Section 10.2 below. To control multiple

heaters on one low voltage thermostat,

See Page 43,

Section 10.3. NOTE: In order to control multiple heat-
ers on one low voltage thermostat, the low voltage
terminals on each heater must be connected as
shown in detail. Heater must be grounded in accor-
dance with applicable codes: United States: refer to
National Electrical Code

®

NFPA 70 - latest revision

Canada: refer to Canadian Electrical Code, CSA
C22.1 Part I - latest revision.If any of the original
internal wiring must be replaced, it must be replaced
with wiring materials having a temperature rating of at
least 105° C and 600 V.

10.1 Line Voltage Thermostat Wiring

10.2 Low Voltage Thermostat with One Burner

DANGER

Electrical Shock Hazard

Disconnect electric before service.

Heater must be properly grounded.

Failure to follow these instructions can result
in death or electrical shock.

Line Voltage

Thermostat

Gnd.

Gnd.

120 V-60 Hz

Supply Circuit

H

N

H

N

Gnd.

L1

L2

T

Low Voltage

Terminal Detail

On All Burners

Gnd.

120 V-60 Hz

Supply Circuit

H

N

Gnd.

L1

L2

Low Voltage

Terminal Detail

Low Voltage

Thermostat

T