Fuel consumption, Fuel pipe sizing, Consumo de combustible – Rheem RESIDENTIAL GENERATOR SYSTEM GEN12S User Manual

Page 12: Dimensiones de la cañería de, Consommation de combustible, Grosseur du tuyau de combust, Fuel consumption fuel pipe sizing

Advertising
background image

Fuel Consumption

See Figure 7 for estimated fuel supply requirements at half
and full load for both natural gas and LP vapor.

Fuel Pipe Sizing

Figures 8 and 9 provide the maximum capacity of pipe in
cubic feet of gas per hour for gas pressures of 0.5 psi or
less and a pressure drop of 0.3 in. water column. Specific
gravity of gas is shown.

Listed values compensate for a nominal amount of
restriction from bends, fittings, etc. If an unusual number of
fittings, bends, or other restrictions are used, please refer to
federal and local codes.

10

NPT

10ft

15ft

20ft

30ft

40ft

50ft

60ft

70ft

80ft

90ft

100ft

3/4”

277

192

158

126

107

95

87

79

74

69

65

1”

428

360

293

236

202

180

164

151

139

129

123

Liquid Propane (LP) (sg=1.50)

Figure 9 — LIQUID PROPANE (LP) GAS Pipe Size - Gas Flow Chart, in cubic feet per hour

Natural Gas*

LP Vapor**

1/2 Load

Full Load

1/2 Load

Full Load

12kW

102

195

41

79

15kW

140

218

66

96

* = Natural Gas is in cubic feet per hour
** = LP Vapor is in cubic feet per hour

Figure 7 — Fuel Supply Requirements

NPT

10ft

15ft

20ft

30ft

40ft

50ft

60ft

70ft

80ft

90ft

100ft

3/4”

346

293

240

192

163

145

132

120

113

106

99

1”

653

549

446

360

307

274

250

230

211

197

187

Natural Gas (sg=0.65)

Figure 8 — NATURAL GAS (NG) Pipe Size - Gas Flow Chart, in cubic feet per hour

Advertising