System Control Panel

Figure 11 depicts the generator system control panel, located
inside the generator housing. Below are brief descriptions of
the controls used during installation. More information may
be found in the Operator’s Manual.

System Switch

This two-position switch is the most important control on
the system and is used as follows:

• “AUTO” position is the normal operating position. If a

utility power outage is sensed, the system will start the
generator. When utility power is restored, lets the
engine stabilize internal temperatures, shuts off the
generator, and waits for the next utility power outage.

• “OFF” position turns off running generator, prevents

unit from starting and resets any detected faults.

15 Amp Fuse

Protects the generator system DC control circuits. If the fuse
has ‘blown’ (melted open) or was removed, the engine
cannot crank or start. Replace the fuse using only an
identical ATO 15A fuse. One spare fuse is supplied with the
unit.

Before Initial Start-up

Engine Oil
This engine is shipped from the factory filled with the
recommended oil. Before starting the engine, check oil level
and ensure that engine is serviced as described in the engine
operator’s manual.

Oil Considerations
Your generator system is equipped with an engine that has
been pre-run at the factory.

The system is filled with synthetic oil (API SJ/CF 5W-30W).
This allows for system operation in the widest range of
temperature and climate conditions.

NOTE: The use of synthetic oil does not alter the required oil
change intervals described in the engine operator’s manual.

Battery Connection
The generator system is supplied with a 12 Volt DC, AGM
type, 55 Amp-Hour, valve regulated battery. It is a sealed,
lead-acid rechargeable battery. It is installed in the unit and
the battery cables are connected at the factory. The unit’s
15 Amp fuse, which isolates the battery and prevents the unit
from starting, has been removed for shipping. The battery will
lose some charge charge prior to installation of the generator.
If battery voltage is below 12 Volts, charge the battery.

IMPORTANT: If battery voltage is below 5 Volts, it may not
take a charge and you will need a new battery.

Charging the Battery

If it is necessary to charge the battery, proceed as follows:

1. Set generator's system switch to OFF.

2. Remove 15 Amp fuse from control panel.

3. Disconnect negative battery cable to negative battery

terminal (indicated by NEGATIVE, NEG, or (-).

4. Charge battery with battery charger at 2 Amps until

battery holds 12 Volts.

NOTE: DO NOT exceed 13.7 Volts charging.

• DO NOT attempt to jump start the battery.
• Damage to equipment resulting from failure to follow this

instruction will void warranty.

NOTICE

Failure to disconnect negative battery cable will result in
equipment failure.

• Refer to engine manual for oil fill information.
• Damage to equipment resulting from failure to follow this

instruction will void warranty.

NOTICE

Any attempt to crank or start the engine before it has been
properly serviced with the recommended oil will result in
equipment failure.

Manual Over-Ride

Switch

Set Exercise

Switch

System Switch

Digital Display

15 Amp Fuse

Service Tool

Circuit

Breaker

Figure 11 — Generator System Control Panel