at test pressures equal to or less than 1/2 psi (3.45
kPa). Relieve test pressure in the gas supply line prior
to reconnecting the heater and its manual shut-off
valve to the gas supply line. FAILURE TO FOLLOW
THIS PROCEDURE MAY DAMAGE THE GAS
VALVES
. Over pressurized gas valves are not cov-
ered by warranty. The heater and its gas connections
shall be leak-tested before placing the appliance in
operation. Use soapy water for leak test. DO NOT use
an open flame.

Reversing Gas Supply Connection

Reversing the standard fuel connection from the left-
hand to the right-hand side is a simple field operation.

1. Disconnect all electrical power from the heater (if

applicable).

2. Disconnect the main gas pipe from the heater (if

applicable).

3. Remove the left and right front panels from the

heater.

4. Locate the main gas line that traverses across the

heater above the manifold risers.

5. Remove the pipe cap from the right-hand end of

the main gas line.

21

Gas Supply

Gas piping must have a sediment trap ahead of the
heater gas controls, and a manual shut-off valve lo-
cated outside the heater jacket. It is recommended
that a union be installed in the gas supply piping adja-
cent to the heater for servicing. A pounds-to-inches
regulator must be installed to reduce the gas supply
pressure to a maximum of 10.5 in. WC for natural gas
and 13.0 in. WC for propane gas. The regulator should
be placed a minimum distance of 10 times the pipe
diameter up-stream of the heater gas controls. Refer
to Table K for maximum pipe lengths.

Gas Supply Connection

The heater must be isolated from the gas supply pip-
ing system by closing the manual shut-off valve during
any pressure testing of the gas supply piping system

CAUTION: The heater must be disconnected from

the gas supply during any pressure testing of the gas
supply system at test pressures in excess of 1/2 psi
(3.45 kPa).

Fig. 16: Gas Supply Connection

CAUTION: Do not use Teflon tape on gas line pipe

thread. A pipe compound rated for use with natural
and propane gases is recommended. Apply
sparingly only on male pipe ends, leaving the two
end threads bare.

CAUTION: Support gas supply piping with

hangers, not by the heater or its accessories. Make
sure the gas piping is protected from physical
damage and freezing, where required.

3/4"

1”

1-1/4”

1-1/2”

2”

2-1/2”

Model

No.

N

P

N

P

N

P

N

P

N

P

N

P

302B

15

25

35

85

150

380

360

--

--

--

--

--

402B

--

15

25

60

100

260

250

--

--

--

--

--

502B

--

--

--

--

65

150

130

360

500

--

--

--

652B

--

--

--

--

45

100

95

250

340

--

--

--

752B

--

--

--

--

35

80

75

180

260

600

--

--

902B

--

--

--

--

20

45

45

110

150

360

400

--

Table K: Maximum Equivalent Pipe Length

DANGER: Make sure the gas on which the heater

will operate is the same type as specified on the
heater’s rating plate.

Natural gas – 1,000 BTU per ft

3

, .60 specific gravity at 0.5 in. WC pressure drop

Propane gas – 2,500 BTU per ft

3

, 1.53 specific gravity at 0.6 in. WC pressure drop

Advertising
This manual is related to the following products: