Detection

Delay

Fault

Flow Switch

Blower Switch

Factory Option

External Interlock

CWS/CWR

Ignition Lockout

*Toggles Between /

Hi Delta

PVC Vent Limit-CHX

Manual High Limit

Auto High Limit

Low Water Cut-off

Vent Pressure

Low Gas Pressure

High Gas Pressure

Controller Alarm

Power On / No CFH

System Normal

Standby / WebSite*

Power On / CFH

System Normal

CFH Active / WebSite*

6

Internal Cntrl Fault

Internal Cntrl Fault

Recycle/Reset Cntrl, Replace Control

Condition

LCD Display Without Fault

4

Low HSI Current

Low HSI Current

Check HSI Current, Replace HSI, Recycle Power, Replace Ign.

5

Low 24VAC

Low 24 VAC

Check Power Supply, Check Transformer

2

Flame - No CFH

Flame - No CFH

Shut Off Gas Supply, Recycle Power

3

Ignition Lockout

Ignition Lockout

Recycle/Reset Cntrl, Push Reset Button

Field

Interlock #

Flashes

LCD Display Readout With Fault

1

Low Air

Low Air Fault

Check Blower, Check Filter, Check Air Sw. Hose

1

Ignition Lockout

Display actual Fault Flash Code

Recycle/Reset Control, Push Reset Button

See Table Below

90

Field Interlock Err

Check Louvers, Check Comb. Damper, Check

Extractor Sw.

3

CWS/CWR Fault

Confirm Inlet Temp, Reset CWS/CWR Cntrl

3

Blower Air Sw. Fault

Check Air Filter, Check Blower, Check Air Sw. Hose

3

Factory Option Fault

Check Factory Data, Check Wiring Diagram, Check

Freeze Control, Check Water Pressure

1

Controller Alarm

See Control Display

3

Water Flow Sw Fault

Check Boiler Pump, Purge Air, Replace Flow Switch

1

Lo Gas Press Fault

Confirm Settings, Check Supply Gas, Reset LGPS

1

Hi Gas Press Fault

Confirm Settings, Check Supply Gas,

1

Lo Water Cutoff Err

Purge Air, Check Pump, Chk Isolation Valve,

Reset LWCO

1

Vent Pressure Fault

Blocked Vent, Check Vent System

1

Man Hi Limit Fault

Confirm Settings, Reset Hi Limit

1

Auto Hi Limit Fault

Confirm Settings, Check Pump

LCD Display Readout With Fault

1

Cond Drain Blocked/Vent Temp Limit Err

Check Drain Switch, Check Drain/Check Vent System

Table R: UDB Fault Messages