Raypak 240692 User Manual

Page 13

Advertising
background image

FIELD WIRING

Single-Stage (On/Off) Boilers

- All stage connections on the control

board are connected at the {TH}
(Thermostat) location on the
boiler wiring diagram.

Multiple-Stage Boilers

- First stage connections on the

control board are connected at
the {TH} (Thermostat) location
on the boiler wiring diagram.

- Second (or third, etc.) stage

connections on the control
board are connected at the
locations shown on the
boiler wiring diagram.

Utilize Shielded Cable

Outdoor Air Temperature
Sensor (see NOTE 4)
Water Temperature
Sensor

P5

Stage 1

Stage 2

Stage 3

Stage 4

1
2
3
4
5
6
7
8

Stage 5

Stage 6

Stage 7

Stage 8

Pump Relay
Pilot Duty Only
2.5 Amp Max
250V Max

Thermostat

(Jumpered) or

Building Management System

Outdoor Temp

Water Temp

1
2
3

P1

1
2

P4

P6

1
2
3
4
5
6
7
8

P2

1
2
3
4

Notes:

1. Tighten terminal strip clamping screws to 4 in-lbs. Breakage from over torquing is not covered under warranty.

2. Use copper conductors only.

3. For supply connections, use wires sized on the basis of 60°C (140°F) ampacity and rated a min. 90°C (194°F).

4. The outdoor sensor must be connected, otherwise a sensor error will be displayed.

13